Payment Terms | T/T, Western Union, MoneyGram |
Supply Ability | 10000 PCs / Month |
Packaging Details | Standard Export Carton Box |
Name | MV Current Transformer Instrument |
Rated primary current | 10-4000A |
Class | 0.2s , 0.5 |
Standards | 50Hz or 60Hz |
Rated load | Rated load ≤40VA |
Application | Current measurement |
Brand Name | GFUVE |
Model Number | GFLZZ0956-10C4 |
Certification | CE , ISO9001 |
Place of Origin | BEIJING CHINA |
View Detail Information
Explore similar products
LZZW3-35Q Instrument Multi Ratio Current Transformer Secondary Output High
Class 0.2s MV Interposing Current Transformer Instrument Durable Measurement
Medium Voltage Instrument Current Transformer Metering Electric Energy 30 Years
High Voltage Poxy Resin Cast Outdoor Electromagnetic Instrument Current
Product Specification
Payment Terms | T/T, Western Union, MoneyGram | Supply Ability | 10000 PCs / Month |
Packaging Details | Standard Export Carton Box | Name | MV Current Transformer Instrument |
Rated primary current | 10-4000A | Class | 0.2s , 0.5 |
Standards | 50Hz or 60Hz | Rated load | Rated load ≤40VA |
Application | Current measurement | Brand Name | GFUVE |
Model Number | GFLZZ0956-10C4 | Certification | CE , ISO9001 |
Place of Origin | BEIJING CHINA | ||
High Light | current potential transformer ,electromagnetic potential transformer |
Class 0.2s Mid Voltage Current Transformer Measurement Instrument
The current transformer of the type GFLZZ0956-10C4 is casting resins and fully enclosed . It is used for metering electric energy and current , relay protection in the electrical system up to rated frequency 50Hz of 60Hz . The current instrument transformers can be executed according to the standards IEC60044-1 , IEC61869-2 and ANSI/IEEE C57.13 .
Rated primary current 10-4000A
Rated load ≤ 40VA
Rated frequency 50Hz or 60Hz
Rated secondary current 5A or 1A
Rated short-time thermal current 100kA, 1S
Rated dynamic current 350KA
Rated insulation level 12/42/75KV
FS ≤10
Ratied Primary Current(A) | Class Combination | Accuracy class and Rated output (VA) |
Short-time thermal current (kA/S) |
Rated dynamic current (kA) |
|||||
0.2S |
0.5S | 0.2 | 0.5 | 5P10 | 5P15 | ||||
10-40 | 0.2(S)/0.2(S)/5P 0.2(S)/0.5(S)/5P 0.5(S)/0.5(S)/5P |
10 | 10 | 10 | 15 | 15 | 10 | 150I1n | 375I1n |
50-75 | 8 | 20 | |||||||
100 | 21 | 52.5 | |||||||
150 | 31.5 | 78.8 | |||||||
200-250 | 40 | 100 | |||||||
300-400 | 15 | 20 | 25 | 15 | 45 | 112.5 | |||
500 | 55 | 130 | |||||||
600 | 30 | 20 | 55 | 130 | |||||
750-1250 | 20 | 25 | 63 | 130 | |||||
1500-2000 | 30 | 40 | 30 | 100 | 200 | ||||
2500-4000 | 20 | 100 | 200 |
Company Details
Business Type:
Manufacturer
Year Established:
2008
Total Annual:
$100,000,000-$150,000,000
Employee Number:
300~350
Ecer Certification:
Active Member
Beijing GFUVE Instrument Transformer Manufacturer Co., Ltd. was established in 2008. It combined design, manufacturing and sales together as one high-tech enterprise. GFUVE Instrument Transformer company mainly produces less than 35kV current transformer and voltage transformer, split core... Beijing GFUVE Instrument Transformer Manufacturer Co., Ltd. was established in 2008. It combined design, manufacturing and sales together as one high-tech enterprise. GFUVE Instrument Transformer company mainly produces less than 35kV current transformer and voltage transformer, split core...
Get in touch with us
Leave a Message, we will call you back quickly!