China 180-290nm Spectrum Fire Alarm Flame Detector OEM / ODM service
China 180-290nm Spectrum Fire Alarm Flame Detector OEM / ODM service

  1. China 180-290nm Spectrum Fire Alarm Flame Detector OEM / ODM service
  2. China 180-290nm Spectrum Fire Alarm Flame Detector OEM / ODM service

180-290nm Spectrum Fire Alarm Flame Detector OEM / ODM service

  1. MOQ: 1PCS
  2. Price: Negotiable
  3. Get Latest Price
Payment Terms T/T, Western Union
Supply Ability 1000PCS/Month
Delivery Time 7 Working days
Packaging Details 360*250*460mm/Carton
Type UV Flame Detector
Spectrum 180~290nm
Power Supply 12-28V DC
Detection Angle 120degree
Certifications CE, RoHS
Installation Ceiling or wall mounted
Alarm Output Relay output, normally open or normally closed
Response Time Less than 3 seconds
Brand Name XHA
Model Number XHARS602
Certification CE
Place of Origin China

View Detail Information

Contact Now Ask for best deal
Get Latest Price Request a quote
  1. Product Details
  2. Company Details

Product Specification

Payment Terms T/T, Western Union Supply Ability 1000PCS/Month
Delivery Time 7 Working days Packaging Details 360*250*460mm/Carton
Type UV Flame Detector Spectrum 180~290nm
Power Supply 12-28V DC Detection Angle 120degree
Certifications CE, RoHS Installation Ceiling or wall mounted
Alarm Output Relay output, normally open or normally closed Response Time Less than 3 seconds
Brand Name XHA Model Number XHARS602
Certification CE Place of Origin China
High Light 180nm Spectrum Fire Alarm Flame Detector290nm Spectrum Fire Alarm Flame DetectorFire Alarm Flame Detector OEM

Effective Fire Detection With Spectrum Of 180-290nm UV Ultraviolet Fire Alarm Flame Detector

 

 




Introduction

 

The detector employs a UV photosensitive tube to detect the ultraviolet rays emitted by flames. This allows it to rapidly identify the presence of fire with a high degree of accuracy.The UV sensing mechanism enables the detector to provide a fast response time, crucial for applications involving flammable or explosive materials.The detector is designed to be immune to false alarms caused by factors such as sunlight, dust, oil, fumes, and humidity. It also provides a dry contact relay output that can be directly connected to a fire alarm control panel, allowing for immediate alarm notification and system integration.

This Ultraviolet Flame Detector is primarily designed for use in high-hazard environments where flammable or explosive materials are handled or stored, such as:

Petrochemical plants
Munitions factories
Oil and gas processing facilities
Chemical storage warehouses
Fueling stations
Other industrial or commercial settings with a high risk of fire.



Specification
 
Operating Voltage Range: 12 to 28 VDC Volts
Standby Current: ≤10 mA @ 24 VDC
Alarm Current ≤30 mA @ 24 VDC
Spectrum: 180~290nm
Detection Angle: 120 degree
Detection Sensitivity: Grade I, 25m@flame (Container 33cmX33cm,Height 5cm with 2Kg ethanol )
Relay Contact Load: 1A@DC24V
Normal Status: LED blinking in 5 seconds interval
Alarm Status: LED lit steady
Operating Humidity Range: 10% to 93% Relative Humidity, Non-condensing
Operating Temperature Range: -20°C to 55°C
 

 Ultroviolet Flame Detector with Relay Output for Fire Alarm System

Installation
 
NOTE: All wiring must conform to applicable local codes, ordinances, and regulations. Mounting Indoor Wall or Ceiling Products.
1. Attach mounting base to ceiling or wall.
2. Connect field wiring to terminals:
Terminal 1: Relay Output -COM (ZONE+)
Terminal 2: Relay Output - NO/NC (ZONE-)
Terminal 3: DC Power -
Terminal 4: DC Power +
3. To attach product to mounting base.
4. Secure product by tightening the two mounting screws in the front of the product housing.
5. The detector can be connected with Security alarm panel as Figure3. Relay output signal can be changed from Normal Close (NC) to Normal Open (NO) by Jump JP1 on the PCB board.
6. The detector can be connected with conventional alarm panel as Figure 4. One 4.7K ohm resistor should be connected as End of Line (EOL) resistor at the last detector.
7. After the installation, power on the detector, use lighter or candle to test the detector within 3 meters.
 

Application in Conventional Fire Alarm system

Ultroviolet Flame Detector with Relay Output for Fire Alarm SystemUltroviolet Flame Detector with Relay Output for Fire Alarm System

Product Range

Conventional Fire Alarm System
Addressable fire alarm system
Gas Extinguishing control system
Beam Detector
4 wire smoke detectors with relay output.
2 wire Conventional smoke and heat detectors
Explosion-proof flame detector for fire alarm system
Standalone smoke detectors and combustable gas detector




Service

1. OEM &ODM service.
2. Provide technical support and after-sale service.
3. 1 year warranty.
4. Normally 15 working days lead time.

5. Welcome sample order.



 

Company Details

Bronze Gleitlager

,

Bronze Sleeve Bushings

 and 

Graphite Plugged Bushings

 from Quality China Factory
  • Year Established:

    2001

  • Total Annual:

    4300000-7140000

  • Employee Number:

    40~50

  • Ecer Certification:

    Verified Supplier

We sepecializes in design and manufacture of high quality fire protection solutions for commerical, industrial and domestic applications. we have nearly 20 years experience in the field of fire protection industry.Everlasting desire for innovation drives our company's product development progres... We sepecializes in design and manufacture of high quality fire protection solutions for commerical, industrial and domestic applications. we have nearly 20 years experience in the field of fire protection industry.Everlasting desire for innovation drives our company's product development progres...

+ Read More

Get in touch with us

  • Reach Us
  • Shenzhen Xinhe'an Technology Co., Ltd.
  • 406,Jude Building,Zhengfeng South Road,Fuyong Street,Bao'An District, Shenzhen City, Guangdong Province. China,518103
  • https://www.xhafiresafety.com/

Leave a Message, we will call you back quickly!

Email

Check your email

Phone Number

Check your phone number

Requirement Details

Your message must be between 20-3,000 characters!

Submit Requirement