Payment Terms | T/T |
Supply Ability | 400 sets per month |
Delivery Time | 5-10 working days |
Packaging Details | Transport Case + Plywood Case |
Product name | CT Analyzer, CT Tester, CT/VT Test Set |
Current output | 0-12A(RMS), 36A(peak value) |
Voltage output | 0-180V(RMS) |
Measuring Accuracy of CT Ratio | ±0.05% |
Max. Knee-point Voltage | 40kV |
Operation | local mode + PC mode |
Brand Name | HAOMAI |
Model Number | CTP-200P |
Certification | ISO9001:2015,m Test Report, Calibration Report |
Place of Origin | China |
View Detail Information
Explore similar products
ANSI Multifunctional CT PT Analyser , Multi Ratio Transformer CT Testing
9kg Multitap CT PT Current Transformer Analyzer IEC Test Standard
HAOMAI Multiratio Instrument Transformer Test Set 0-180V RMS
ISO9001 Automatic Instrument Transformer Test Set 36A Multifunctional
Product Specification
Payment Terms | T/T | Supply Ability | 400 sets per month |
Delivery Time | 5-10 working days | Packaging Details | Transport Case + Plywood Case |
Product name | CT Analyzer, CT Tester, CT/VT Test Set | Current output | 0-12A(RMS), 36A(peak value) |
Voltage output | 0-180V(RMS) | Measuring Accuracy of CT Ratio | ±0.05% |
Max. Knee-point Voltage | 40kV | Operation | local mode + PC mode |
Brand Name | HAOMAI | Model Number | CTP-200P |
Certification | ISO9001:2015,m Test Report, Calibration Report | Place of Origin | China |
High Light | 120V Current Transformer Test Equipment ,60Hz Current Transformer Test Equipment ,Portable CT VT Analyzer |
Portable Current Transformer Test Set
Model: CTP-200P
The Portable Current Transformer Test Set CTP-200P is designed to automatically measure the related parameters of current transformer(CT), such as excitation characteristic, turns ratio, polarity, winding resistance, saturated and unsaturated inductivity, remanence flux percentage, accuracy limiting factor(ALF) or instrument security factor(FS), secondary burden etc.
The CTP-200P also allows the simulation of ratio, secondary time constant, ALF and FS at free adjustable burden and primary current also after the test with the determined test results.
The Portable Current Transformer Test Set CTP-200P also supports voltage transformer(VT) test. The ratio, polarity, excitation characteristic and winding resistance of VT can be tested.
The Portable Current Transformer Test Set CTP-200P is rugged and immune to electrical noise interference in high voltage substations.
Main Features
●Able to test Protection CTs, Measuring CTs, PR/PX CTs, TPS/TPX/TPY/TPZ CTs and inductive VTs defined in IEC61869-2, IEC60044-1,60044-6, IEC61869-3, IEC60044-2, IEEE/ANSI C57.13
●Test excitation characteristic and error curve based on low-frequency measurement principle
●Measure ratio, polarity, ratio error and phase displacement error based on voltage method
●Adopt patented multifunctional rotary mouse to replace the keypad
●Sunlight readable 5.7-inche LCD screen for display
●Adopt DSP, ARM and embedded LINUX operation system
●Both local test and PC remote test available
●Higher measurement accuracy: 0.05 %
●The max. tested knee-point voltage of CT up to 40kV
●Performs secondary burden tests
●Automatic demagnetization of CT
●Print test results directly by built-in thermal printer
●Small and light weight (9kg / 19.84 lbs) for easy transport
Technical Data
●Test Standards: IEC61869-2, IEC60044-1,60044-6, IEC61869-3, IEC60044-2, IEEE/ANSI C57.13
●Maximum Knee Voltage Measurement: 40kV
●Output Range:
voltage: 0~180V(RMS)
current: 0~12A(RMS), 36A(peak value)
●Voltage Measurement Accuracy: ±0.05%
●CT Ratio Measurement:
range:1~30000
accuracy: ±0.05%
●PT Ratio Measurement:
range:1~10000
accuracy: ±0.05%
●Phase Measurement:
accuracy: ±2min
resolution: 0.01min
●Secondary Winding Resistance Measurement:
range: 0~300Ω
accuracy: 0.1%±1mΩ
●Burden Measurement:
range: 0~300VA
accuracy: 0.1%±0.1VA
●Memory Capacity: >3000 groups test results
●Power Supply
Nominal input voltage | customized(AC220V/230V/120V±10%, 1-phase) |
Nominal frequency | 50/60 Hz |
Rated current | 10A at 230V / 12A at 120V |
Connection | standard AC socket (IEC 60320) |
●Environmental Conditions
Operation temperature | 0 ... +50 °C (+32 ... +122 °F) |
Storage temperature | -25 ... +70 °C (-13 ... +158 °F) |
Humidity range | relative humidity 5 ... 95 %, non-condensing |
Vibration | IEC 60068-2-6(20m/s2 at 10 ... 150 Hz) |
●Miscellaneous
Weight | 9kg(19.84 lbs) |
Dimensions (W x H x D, without handle) | 340×300×150mm(13.39x11.81x5.91 in) |
Connection port | 2 USB2.0 ports, 1 communication port |
The software of Portable Current Transformer Test Set CTP-200P is able to run on a PC with Windows operating system. Free of charge for upgrading software version.
The Portable Current Transformer Test Set CTP-200P is housed in a portable, shock and vibration resistance enclosure with handle on side and with wheels and retractable handle.
Company Details
Business Type:
Manufacturer
Year Established:
1999
Total Annual:
16500000-18000000
Employee Number:
230~270
Ecer Certification:
Active Member
HAOMAI ELECTRIC TEST EQUIPMENT CO.,LTD, as a subsidiary of HAOMAI ELECTRIC POWER AUTOMATION CO.,LTD, located in Shenzhen of China, mainly focuses on the sales and services of Protection Relay Test Set, Instrument Transformer Test Set, CT/PT Analyzer, Power Transformer Test Set, Circuit Breaker ... HAOMAI ELECTRIC TEST EQUIPMENT CO.,LTD, as a subsidiary of HAOMAI ELECTRIC POWER AUTOMATION CO.,LTD, located in Shenzhen of China, mainly focuses on the sales and services of Protection Relay Test Set, Instrument Transformer Test Set, CT/PT Analyzer, Power Transformer Test Set, Circuit Breaker ...
Get in touch with us
Leave a Message, we will call you back quickly!