Payment Terms | L/C, D/A, D/P, T/T, Western Union, MoneyGram |
Supply Ability | |
Delivery Time | 2-4 weeks |
Packaging Details | Export standard wooden box (like plywood), no need to fumigate, really suitable for shipping. |
RO frame | SUS304/Carbon steel |
Tank material | SS/FRP (optional) |
Capacity | 30T/H |
Membrane size | 8040 |
Recovery rate | 70% |
Desalination rate | ≥99.5% |
Power | 37KW |
Pipe material | U-PVC/Stainless steel (optional) |
Brand Name | Jufu |
Model Number | JFRO-30T |
Certification | ISO9001 |
Place of Origin | China |
View Detail Information
Explore similar products
500LPH Reverse Osmosis Drinking Water Treatment System One Stage RO Plant
Pure Drinking Water Reverse Osmosis System Desalination Equipment 1.5KW 1000L/h
1000LPH Drinking Water RO System Reverse Osmosis For Bottled Pure Water
500LPH Drinking Water RO System FRP Manual Control For Pure Water
Product Specification
Payment Terms | L/C, D/A, D/P, T/T, Western Union, MoneyGram | Supply Ability | |
Delivery Time | 2-4 weeks | Packaging Details | Export standard wooden box (like plywood), no need to fumigate, really suitable for shipping. |
RO frame | SUS304/Carbon steel | Tank material | SS/FRP (optional) |
Capacity | 30T/H | Membrane size | 8040 |
Recovery rate | 70% | Desalination rate | ≥99.5% |
Power | 37KW | Pipe material | U-PVC/Stainless steel (optional) |
Brand Name | Jufu | Model Number | JFRO-30T |
Certification | ISO9001 | Place of Origin | China |
High Light | 30TPH Drinking Water RO Plant ,30TPH RO Filter System ,One Stage Drinking Water RO Plant |
ISO Certified 30TPH Drinking Water RO Plant One-Stage RO Filter System
What are the important indicators of drinking water reverse osmosis system?
In the selection of reverse osmosis equipment, there is an extremely important index - desalination rate, which determines the quality of produced water. The abolishment rate is the percentage of soluble impurities removed from system influent by reverse osmosis membrane. This number can be seen from the ability of reverse osmosis membranes to filter impurities from water.
In addition, there are organics, microorganisms, solid particles and residual chlorine in the water, which pollute the ro membrane, so it needs to be pretreated to avoid membrane surface blockage and damage and reduce the desalination rate.
Drinking Water RO System workflow:
raw water - raw water tank - raw water booster pump - quartz sand filter - activated carbon filter - scale inhibitor dosing equipment - precision filter - first-stage high pressure pump - first-stage reverse osmosis Host - intermediate water tank - secondary high pressure pump - secondary reverse osmosis host - disinfection system - production water.
Technical specifications of Drinking Water RO System
Model | JFRO-30T |
Host Size | 6000x1200x1800mm (can be customized) |
Power | 37KW |
Power Supply | 220V /380V/460V - 50Hz/60Hz,220V 50Hz can be customized |
Operating Pressure | 1.2~1.5MPa |
Recovery Rate | 70% |
Designed Water Inlet | 42t/h |
Outlet Flow | 30t/h |
Desalination Rate | ≥99.5% |
RO Frame | SUS304/Carbon Steel (Optional) |
Membrane Size | 8040 |
Membrane Elements | DOW /Hydranautics/Troy/ Vontron (Optional) |
Number of Membranes | 30 |
Raw Water Pump | CNP/NYP/GRUNDFOS (Optional) |
High Pressure Pump | CNP/NYP/GRUNDFOS (Optional) |
Tank Material | SS/FRP(Optional) |
Control Valve | Manual/Automatic |
Control Valve Brand | FLECK/RUNXIN |
Membrane Housing | FRP |
Number of Membrane housing | 6 |
Pipe Material | U-PVC/ Stainless steel (Optional) |
Drinking Water RO system Trouble-shooting
possible reason | possible location | pressure drop | Product water flow | salt permeability |
Metal oxide | The first section | usually increases | decline | usually increases |
colloid fouling | The first section | usually increases | decline | usually increases |
fouling | The last section | increases | decline | increases |
Biofouling
| any section | usually decline | increases | Increase |
organic fouling
| all sections | normal | decline | usually increases |
Oxidizing agent (eg: Cl2)
| The first part is the most serious | usually decline | increases | Increase |
Surface wear (carbon particles,sludge) | The first part is the most serious | decline | increases | Increase |
Cracks in O-rings or glued
| random | usually decline | usually decline | Increase |
The recovery rate is too high | all parts | decline | usually decline | Increase |
FAQ:
1. What is the shell film material and specification of drinking water reverse osmosis system?
Material of membrane case: stainless steel and fiberglass (FRP)
Specification of membrane shell: four inch membrane shell 4040 (one core to four core)
8 inch membrane case 8040 (one to seven cores)
2. What are the inlet water quality requirements of drinking water reverse osmosis system?
Inlet water quality requirements:
Turbidity (NTU) ≤1, SDI ≤5 Residual chlorine (mg/L) ≤0.1, Fe2+ (mg/L) ≤4, TOC (mg/L) ≤3
Company Details
Business Type:
Manufacturer,Exporter
Year Established:
2008
Total Annual:
1-10 Mln
Employee Number:
20~100
Ecer Certification:
Active Member
Jufu Water is a Hi-tech enterprise which specialized in integrating Research & Development, Manufacturing, Sales, Engineering installation and Consulting on water treatment and water purification equipment and technologies. Jufu has strong power on know-how solution providing. The w... Jufu Water is a Hi-tech enterprise which specialized in integrating Research & Development, Manufacturing, Sales, Engineering installation and Consulting on water treatment and water purification equipment and technologies. Jufu has strong power on know-how solution providing. The w...
Get in touch with us
Leave a Message, we will call you back quickly!