Payment Terms | T/T, Western Union |
Supply Ability | 1000 PCS/month |
Delivery Time | 30~35 days |
Packaging Details | Plywood case or stretch film +pallet |
Air side heat exchanger type | Finned heat exchanger |
Water side heat exchanger type | Shell heat exchanger |
Supply power | 380v 3N~50Hz |
Refrigerant | R22, R407C and R410A |
Working ambient temperature | -22 ~ +48 ℃ |
Heating capacity range | 19.5~80kW |
Max water outlet temp. | 60° C |
Remark | Modularization |
Compressor brand | Panasonic or invotech brand |
Brand Name | Shenglin |
Model Number | HRF series |
Certification | CE |
Place of Origin | China |
View Detail Information
Explore similar products
3.2kw Swimming Pool Inverter Heat Pump , Low Temperature Heat Pump DN25
Dn25 15kw Air Source Heat Pumps For Swimming Pool Hotel Villa
Hot Water 52KW Rooftop Heat Pump High Temperature Rooftop Hvac Units
5HP 21kW Air Source Heat Pumps , Air Temp Heat Pump 5000L H
Product Specification
Payment Terms | T/T, Western Union | Supply Ability | 1000 PCS/month |
Delivery Time | 30~35 days | Packaging Details | Plywood case or stretch film +pallet |
Air side heat exchanger type | Finned heat exchanger | Water side heat exchanger type | Shell heat exchanger |
Supply power | 380v 3N~50Hz | Refrigerant | R22, R407C and R410A |
Working ambient temperature | -22 ~ +48 ℃ | Heating capacity range | 19.5~80kW |
Max water outlet temp. | 60° C | Remark | Modularization |
Compressor brand | Panasonic or invotech brand | Brand Name | Shenglin |
Model Number | HRF series | Certification | CE |
Place of Origin | China | ||
High Light | 80kW packaged Air Source Heat Pump ,HRF commercial air source heat pump ,R407C modular scroll rooftop package units |
Modular Low Temperature Air Source Heat Pump
Features:
1. Low temperature and high efficiency: ambient temperature -12 °C, outlet temperature 45 °C, energy efficiency ratio ≥ 2.4, ambient temperature -20 °C, outlet water temperature 45 °C energy efficiency ratio ≥ 2.0, comprehensive energy efficiency is higher than Chinese energy conservation certification;
2. Low ambient temperature and high water outlet temperature: ambient temperature -25 °C, the outlet temperature can be as high as 60 °C;
3. Stable and reliable: ambient temperature ≥ 43 °C, water outlet temperature 60 °C, ambient temperature -25 °C, water outlet temperature 60 °C, long-term stable operation;
4. Water route cleanliness: the unit water route and the water side heat transfer water route adopt the full copper design, nowhere to rust, to ensure that the water quality is not affected by the unit pipeline;
5. Advanced technology: dual electronic expansion, 3-way fin temperature sensor, optional humidity sensor to control defrosting;
6. Modularization: modular design allows for free expansion, facilitating investment in phases
Technical paramater:
Type | HRF20HRSPMT5 | HRF36HRSPMT5 | HRF42HRSPMT5 | HRF80HRSPMT5 | |||
Temperature setting range | ℃ | 50°C (default), 25~60°C freely adjustable | |||||
Maximum input power | kW | 7.3 | 12.2 | 14.7 | 29.5 | ||
Maximum input current | A | 12.1 | 22.2 | 25.8 | 49.5 | ||
Power supply | / | 3N~/380V/50Hz | |||||
Refrigerant | / | R22 | |||||
Refrigerant charge | kg | 3.5 | 6.0 | 6.5 | 2x6.5 | ||
Recirculating water pipe diameter | / | Rc1 internal thread | Rc1-1/2 internal thread | Rc1-1/2internal thread | Rc1-1/2internal thread | ||
Water side heat exchanger type | / | High efficiency tank heat exchanger | |||||
Water pipeline maximum pressure | MPa | 1.0 | |||||
Length x width x height | mm | 1225x792x1015 | 1545x950x1272 | 1545x950x1272 | 2000x1060x1976 | ||
Weight | kg | 131 | 245 | 286 | 620 | ||
Noise | dB(A) | 63 | 66 | 66 | 68 | ||
Hot water working condition technical parameters | |||||||
Heating capacity | kW | 19.5 | 36.0 | 41.6 | 80.0 | ||
Hot water | l/h | 419 | 774 | 894 | 1720 | ||
Input power | kW | 4.5 | 8.1 | 9.5 | 18.6 | ||
Rated water flow | m3/h | 3.4 | 6.2 | 7.2 | 13.8 | ||
Water side pressure loss | kPa | 32 | 38 | 45 | 52 | ||
Heating working condition technical parameters | |||||||
Ambient temperature (DB/WB) | Water temperature (In/out) | ||||||
7℃/ 6℃ | 30℃/ 35℃ | Heating capacity | kW | 16.9 | 30.8 | 35.2 | 69.3 |
Input power | kW | 4 | 7.2 | 8.3 | 16.8 | ||
40℃/ 45℃ | Heating capacity | kW | 16.7 | 31.0 | 35.6 | 70 | |
Input power | kW | 4.7 | 8.6 | 9.9 | 20.1 | ||
50℃/ 55℃ | Heating capacity | kW | 16.5 | 30.8 | 35.2 | 69.2 | |
Input power | kW | 5.6 | 10.2 | 11.8 | 23.7 | ||
55℃/ 60℃ | Heating capacity | kW | 16.4 | 30.5 | 35 | 69 | |
Input power | kW | 6 | 10.9 | 12.7 | 25.5 | ||
55℃/ 65℃ | Heating capacity | kW | 16.4 | 30.7 | 35.1 | 69.1 | |
Input power | kW | 6.9 | 12.8 | 14.7 | 29.1 | ||
-12℃/ -14℃ | 36℃/ 41℃ | Heating capacity | kW | 11 | 20.3 | 23.5 | 45.9 |
Input power | kW | 4.1 | 7.4 | 8.6 | 17.3 | ||
55℃/ 60℃ | Heating capacity | kW | 10.5 | 19.7 | 22.8 | 44.8 | |
Input power | kW | 5.3 | 9.8 | 11.3 | 22.8 | ||
Rated water flow(Δ5K/Δ10K) | m3/h | 2.9 / 1.5 | 5.4 / 2.7 | 6.2 / 3.1 | 12.0 / 6 | ||
Water side pressure loss | kPa | 32 | 38 | 45 | 52 |
1. Hot water test condition: dry bulb temperature 20 °C, wet bulb temperature 15 °C; initial water temperature 15 °C, end water temperature 55 °C;
2. Heating test condition 1 : dry bulb temperature 7 °C, wet bulb temperature 6 °C; inlet and outlet water temperature 30/35 °C, 40/45 °C, 55/65 °C;
3. Heating test condition 2: dry bulb temperature -12 °C, wet bulb temperature -14 °C; inlet and outlet water temperature 36/41 °C, 55/60 °C;
4. Product suitable ambient temperature range is: -22 ~ 48 °C
Packing:
![]() | ![]() |
Reference:
Country: Taiwan,China, middle school Model: KFXR-018 UII,KFXR-045UII Application: Domestic hot water | Country: Taiwan,China,residential building Model: KFXR-036UII,KFXR-900UII Application: Domestic hot water |
![]() ![]() | ![]() ![]() |
Country: Beijing, China Model: KFXF-180 UII Application: Breeding heating | Country: Yunan, China Model: / Application: Aloe drying |
![]() ![]() | ![]() ![]() |
Company Details
Business Type:
Manufacturer
Year Established:
2009
Employee Number:
>100
Ecer Certification:
Active Member
Introduction: Shanghai Shenglin is a professional manufacturer and sales of heat exchanger and air conditioning unit since 2009, located in Shanghai, China. Shanghai Shenglin was established in 2009, at the beginning only do HVAC international trading, then from 2012, we ... Introduction: Shanghai Shenglin is a professional manufacturer and sales of heat exchanger and air conditioning unit since 2009, located in Shanghai, China. Shanghai Shenglin was established in 2009, at the beginning only do HVAC international trading, then from 2012, we ...
Get in touch with us
Leave a Message, we will call you back quickly!