Payment Terms | L/C, D/A, D/P, T/T, Western Union, MoneyGram |
Supply Ability | 10000 Set/Sets per Day |
Delivery Time | 7~15 working days |
Packaging Details | Splint wooden cases |
Protection | Lightning |
Wave Form | Pure Sinewave |
Weight | 573KG |
Color | white |
Application | INSTRUMENTATION |
Product name | Online UPS Systems |
Capacity | 100KVA/80KW |
Battery Type | Lead Acid Battery |
Input/output voltage | 380V 400V 415V |
Brand Name | ZGD |
Model Number | ZGD33100 |
Certification | CE/ROSH/GS/TUV/MSDS |
Place of Origin | Guangdong, China |
View Detail Information
Explore similar products
100KVA To 200KVA Low Frequency Online UPS Power Supply TUV certified
Three Phase 10KVA To 100KVA Industrial Uninterruptible Power Supply 380V/400V
Unbalanced Loads Protection 6KVA Online Ups Backup Power Supply ROSH Certified
3 Phase In 1 Phase Out 15000va Low Frequency Online UPS Isolated Secure
Product Specification
Payment Terms | L/C, D/A, D/P, T/T, Western Union, MoneyGram | Supply Ability | 10000 Set/Sets per Day |
Delivery Time | 7~15 working days | Packaging Details | Splint wooden cases |
Protection | Lightning | Wave Form | Pure Sinewave |
Weight | 573KG | Color | white |
Application | INSTRUMENTATION | Product name | Online UPS Systems |
Capacity | 100KVA/80KW | Battery Type | Lead Acid Battery |
Input/output voltage | 380V 400V 415V | Brand Name | ZGD |
Model Number | ZGD33100 | Certification | CE/ROSH/GS/TUV/MSDS |
Place of Origin | Guangdong, China | ||
High Light | 100KVA UPS ,380v UPS ,415v UPS |
Industrial 80KW 100KVA UPS Three Phase 380v 400v 415v Power Supply
ZGD310/ZGD330 provides maximum protection for vital mission-critical networks, security applications (electro- medical)and industrial applications thanks to its outstanding mechanical and electrical design.
The load is powered continuously by the inverter with a filtered, stabilised and regulated sinewave supply. The input and output EMI filters considerably increase the immunity of the load to mains disturbances and surges.
The ZGD310/ZGD330 uses on-line double conversion technology (VFI) with isolation transformer on theinverter output.
The ZGD310/ZGD330 is supplied with Watch & Save 3000 software as standard and can be remotely monitored
using the Power NetGuard system from anywhere in the world. Additional battery extension packs allow the standard
Specification
model | ZGD33 100K | |||||||||||
capacity | 80 KW | |||||||||||
INPUT | ||||||||||||
Nominal Voltage | 3 x 380VAC/400VAC (3Ph + N) | |||||||||||
Acceptable Voltage Range | 305VAC ~ 460VAC | |||||||||||
Frequency | 50/60 Hz ± 10 % | |||||||||||
INVERTER | ||||||||||||
Nominal Voltage | 3 x 380VAC/400VAC (3Ph + N) | |||||||||||
Precision | Stationary: ±1% ; Transitory: ±5% (load variations 100-0-100%) | |||||||||||
Frequency | 50/60 Hz synchronised ±1 % With mains absent ±0.1 Hz | |||||||||||
Max. Synchronisation Speed | ±1 Hz/s | |||||||||||
Waveform | Pure Sinewave | |||||||||||
Total Harmonic Distortion (THDv) | < 2% (Linear Load) ; < 5% (Non-linear Load) | |||||||||||
Phase Displacement | 120º ±1% (balanced load) ; 120º ±2% (imbalances 50% of the load) | |||||||||||
Dynamic Recovery Time | 3 cycles at 98 % of the static value | |||||||||||
Admissible Overload | 110% for 10min; 150% for 60sec ; >160% for 200ms | |||||||||||
Admissible Crest Factor | 3:1 | |||||||||||
Admissible Power Factor | 0.6~1 (inductive or capacitive) | |||||||||||
Current Limit | High overload, short-circuit: RMS Voltage Limit ; High Crest-Factor current: Peak Voltage Limit | |||||||||||
STATIC BYPASS | ||||||||||||
Type | Solid state | |||||||||||
Voltage | 3 x 380VAC/400VAC (3Ph + N) | |||||||||||
Frequency | 50/60 Hz | |||||||||||
Activation Criterion | Microprocessor control | |||||||||||
Transfer Time | Zero | |||||||||||
Admissible Overload | 150% for 1 hour; 180% for 30sec; >200% for 200ms | |||||||||||
Transfer to Bypass | Immediate, for overloads above 160% | |||||||||||
Retransfer | Automatic after alarm clear | |||||||||||
BATTERY & CHARGER | ||||||||||||
Battery Type and Numbers | 12VDC x 32 pcs (29~32 pcs adjustable) | |||||||||||
Nominal Battery Voltage | 384 VDC (Based on 32pcs batteries) | |||||||||||
Charging Method | CC/CV | |||||||||||
Charging Current | Default: 10A. Max. 40A | |||||||||||
Charging Voltage | 432 VDC (Based on 32pcs batteries) |
Packing & Delivery
Company Details
Business Type:
Manufacturer,Exporter,Seller
Total Annual:
1000000-5000000
Employee Number:
zgd001~zgd500
Ecer Certification:
Site Member
As a manufacturer with over 10 years of experience, Shenzhen ZGD Technology Co., Ltd. has more than 10 production lines which can produce 100,000 pieces of UPS every month. Over 10% of our staff members are engineers and professional technicians and more than 400 are skilled workers. Our company spe... As a manufacturer with over 10 years of experience, Shenzhen ZGD Technology Co., Ltd. has more than 10 production lines which can produce 100,000 pieces of UPS every month. Over 10% of our staff members are engineers and professional technicians and more than 400 are skilled workers. Our company spe...
Get in touch with us
Leave a Message, we will call you back quickly!