Payment Terms | L/C, T/T, Western Union |
Supply Ability | 1500sets per week |
Delivery Time | 1500sets within 1 week |
Packaging Details | export standard package |
Input operating voltage | AC220V |
Inpting voltage frequencyut opera | 50HZ |
Allowable fluctuation range of input operating voltage | ±20% |
Overall power consumption | ≤10W |
Time to trip | <35ms |
Insulation impedance | >100MΩ/ DC500V |
Brand Name | Tianyihongda |
Model Number | TYHD-FTU-CB |
Certification | type test report |
Place of Origin | Beijing,China |
View Detail Information
Explore similar products
DTU Network Feeder Power Distribution Terminal Automation Device High Performanc
DTU Power Remote Transmission Unit , High Stability Network Termination Unit
High Frequency Power Distribution Terminal 18 Lines Remote Control Self Check
Wireless Transmission Power Distribution Terminal Feeder Unit For Circuit
Product Specification
Payment Terms | L/C, T/T, Western Union | Supply Ability | 1500sets per week |
Delivery Time | 1500sets within 1 week | Packaging Details | export standard package |
Input operating voltage | AC220V | Inpting voltage frequencyut opera | 50HZ |
Allowable fluctuation range of input operating voltage | ±20% | Overall power consumption | ≤10W |
Time to trip | <35ms | Insulation impedance | >100MΩ/ DC500V |
Brand Name | Tianyihongda | Model Number | TYHD-FTU-CB |
Certification | type test report | Place of Origin | Beijing,China |
High Light | feeder remote terminal unit ,remote control terminal |
Wireless transmission and remote control power distribution terminal connecting circuit breaker on pole
This is a new HV switch control device equipped with both the imported DSP high-speed sampling chips and the high-performance ARM chips, and can fast and stably finish the monitoring on the switch. It boasts of such functions as the protection, measuring, controlling, monitoring, communication, remote control and so on and features high integration level, flexible configuration and user-friendly interface, widely applied to the radiant and ring network power supply systems to help the systems identify transient and permanent line faults, eliminate the impact of transient line faults automatically, isolate the permanent fault segments to avoid prolonged power failure in large area, and automatically recover the power supply in fault-free areas, so as to realize the automation of power distribution network in a economical and practical way.
Operating ambient temperature: From -40℃ to +85℃.
Relative air humidity: The air humidity can not exceed 50% at the maximum temperature and higher air humidity is allowed at lower temperature. For example, the air humidity shall be 90% at +20℃ as it may occasionally cause condensation with the temperature chan
ges.Atmospheric pressure: 66kPa~108kPa.
Operating environment: no explosive and flammable materials, no air or conductive dust which will damage the insulation and cause metal corrosion, no serious mold and no severe vibration sources, with measures to defend against rain, snow, wind, sand, dust and static electricity.
Table for Selection of Fixed Values for Zero-sequence Protection Current
Length of cable at switch load side (m) | 50 | 100 | 150 | 200 | 250 | 300 | 350 | 400 | 450 | |
Length of overhead line at switch load side (m) | <1000 | <4000 | ||||||||
Fixed value (A) | 0.2 | 0.4 | 0.6 | 0.8 | 1.0 | 1.2 | 1.4 | 1.6 | 1.8 | 2.0 |
Length of cable at switch load side (m) | 480 | 500 | 550 | 600 | 650 | 700 | 750 | 800 | 850 | 900 |
Fixed value (A) | 2.2 | 2.4 | 2.6 | 2.8 | 3.0 | 3.2 | 3.4 | 3.6 | 3.8 | 4.0 |
Calculation formula for fixed values: Fixed value of current =1.5×3×(S1×L1+S2×L2)
L1 is the total length of overhead line at boundary switch load side. S1 is the empirical value of capacitive current of overhead line per km per phase. The recommended value is 0.02A/km.
L2 is the total length of cable at boundary switch load side. S2 is the empirical value of capacitive current of cable per km per phase. The recommended value is 1A/km.
Selection of Fixed Values for Zero-sequence Protection Delay
Choose 1S when the neutral point is not earthed or earthed by arc suppression coil. Choose OS or lower when the neutral point is earthed by low resistance.
The calculation of fixed values for zero-sequence protection current only depends on the direct earth capacitance of cable or overhead line at switch load side. The table above is the results of approximate amount multiplied by safety factor. Users can calculate personally according to the actual condition of the line at switch load side. If there are both cable and overhead line at switch load side, add their direct earth capacitances together. The safety factor shall be chosen between 1.5~3 (It is recommended that a larger safety factor shall be chosen when the fixed value is relatively small, while a smaller one shall be chosen when the fixed value is relatively large.)
Type Test Items
1. appearance and structure 2.function 3. electrical device performance 4.low temperature performance 5.high temperature performance 6.alternating temperature humidity7.vibrationendurance 8.incline drop test 9. electrical device life 10. static electricity and elecro-discharge immunity test 11.radio frequency electromagnetic field radiated immunity test 12.surge impact immunity test 13. power frequency magnetic field immunity test. 14. Adjacent interference test 15.short-circuit withstand impact test 16. fire hazard test 17. power consumption test 18. protection grade test 19. gripping strength test of grip structure.
Company Details
Business Type:
Manufacturer,Exporter,Seller
Year Established:
2014
Total Annual:
3000000-5000000
Employee Number:
150~180
Ecer Certification:
Site Member
Beijing TIANYIHONGDA Science & Technology Development Co., LTD is located in Lize Business Circle area, a prosperous business area in the center of Beijing City, China. is a high and advanced technology enterprise which is professionally engaged in research, production, sales and service of adva... Beijing TIANYIHONGDA Science & Technology Development Co., LTD is located in Lize Business Circle area, a prosperous business area in the center of Beijing City, China. is a high and advanced technology enterprise which is professionally engaged in research, production, sales and service of adva...
Get in touch with us
Leave a Message, we will call you back quickly!