China factories

China factory - Shenzhen Daxin Intelligent Equipment Technology Co., Ltd

Shenzhen Daxin Intelligent Equipment Technology Co., Ltd

  • China,Shenzhen
  • Verified Supplier

Leave a Message

we will call you back quickly!

Submit Requirement
China Outdoor Wall-Mounted Power Supply Outdoor Energy Storage Communication Power
China Outdoor Wall-Mounted Power Supply Outdoor Energy Storage Communication Power

  1. China Outdoor Wall-Mounted Power Supply Outdoor Energy Storage Communication Power
  2. China Outdoor Wall-Mounted Power Supply Outdoor Energy Storage Communication Power
  3. China Outdoor Wall-Mounted Power Supply Outdoor Energy Storage Communication Power

Outdoor Wall-Mounted Power Supply Outdoor Energy Storage Communication Power

  1. MOQ: 1pcs
  2. Price:
  3. Get Latest Price
Payment Terms L/C, T/T
Supply Ability 10000pcs/month
Packaging Details Wooden pallet+cardboard box
Name Communication power supply
Battery Shelf 19-inch mount
Certificates CE
Output Voltage DC 48V
Lock Type Round lock
Rack 19 inch rack
Hinge Concealed embedded hinge
Size Customized
Function Power Supply Cabinet for Telecomm Base
Cooling System Fan
Brand Name daxin
Model Number DX48150
Certification CE,UL
Place of Origin shenzhen

View Detail Information

Contact Now Ask for best deal
Get Latest Price Request a quote
  1. Product Details
  2. Company Details

Product Specification

Payment Terms L/C, T/T Supply Ability 10000pcs/month
Packaging Details Wooden pallet+cardboard box Name Communication power supply
Battery Shelf 19-inch mount Certificates CE
Output Voltage DC 48V Lock Type Round lock
Rack 19 inch rack Hinge Concealed embedded hinge
Size Customized Function Power Supply Cabinet for Telecomm Base
Cooling System Fan Brand Name daxin
Model Number DX48150 Certification CE,UL
Place of Origin shenzhen
High Light 19 inch cabinet power supply19 inch communication power supply

 

Outdoor Wall-Mounted Power Supply Outdoor Energy Storage Communication Power Supply/Outdoor Wall-Mounted Power Supply

 

 

  Principles of Power System

   The system input is sent to the rectifier module input through a 63A/2P circuit breaker. Parallel AC C-level lightning protection is used for lightning protection at the input end.

  The rectifier module operates in parallel, and its DC output is connected through a busbar to supply two backup battery packs and DC loads. DC loads are controlled by fuses or air switches, providing users with on/off control for each load and protection against overload and short circuits.

  Under normal system conditions, various parameters of the rectifier module and distribution unit are controlled by the monitoring module and operate according to their predetermined parameters or user commands. If the mains power fails, the system will switch to battery power supply. As the battery discharges, the voltage at the battery end begins to drop. When the battery voltage drops to a power down voltage point, the monitoring module controls the power down contactor to operate and cut off the load; When the battery voltage drops to the battery protection voltage point, the monitoring module controls the action of the secondary power-off contactor, cutting off the connection between the power system and the battery, protecting the battery from excessive discharge. At this time, the power system will stop working. When the external mains power is restored and the rectifier module resumes output, the system will resume normal operation. The monitoring module can detect and control the working status of the entire power distribution system. User commands can be issued through the keyboard on the monitoring module panel, local backend PC, and remote central control room. The system's working status and parameters can be displayed on the monitoring module LCD screen, local backend PC, and remote central control room. The system can collect various environmental variables, including smoke, door magnets, water immersion, temperature, and humidity, by configuring appropriate sensorsReport.

 

Overall structure

   The power supply system plug-in frame (height * width * depth) are 700mm * 580mm * 350mm. It consists of an AC distribution unit, a monitoring unit, a rectifier module unit, and a DC distribution unit, and can be installed in floor, wall, pole, and other ways. Left and right air ducts, module with built-in fan for forced heat dissipation, IP55, built-in temperature control system. Provide installation space for one set of 50AH ferroelectric batteries or four 38AH lead-acid batteries.

   Monitoring scheme: Monitor the RS485 ports in the north and south directions, dry contacts, and battery cell detection (optional) all led to the monitoring panel

   Operation and maintenance method: Pre maintenance, rectifier module can be hot swappable.

 

component configuration notes
AC distribution unit Communication on lightning protection Grade C:20~40KA  
Communication input 63A/2P*2 The limit breaking ability ICU ≥6kA, the short circuit segmenting ability Ics ≥6kA
Intelligent instrument (optional) DDS3366P-3Type single-phase three-way electric energy meter Can detect AC voltage, current, electrical energy, three-way input switch values, etc.
Rectifier module RM4850*3  
Monitoring unit SM32  
DC distribution unit Battery switch 100A/1P*2 Ultimate breaking capacity Icu ≥ 20kA and operating short-circuit breaking capacity Ics ≥ 15kA
Power off once 63A/1P*1;32/1P*2;20/1P*2  
Various user configurations are optional
second disconnection 20A/1P*1;10A/1P*2; Limit breaking capacity ICU ≥6 ka and running short circuit breaking capacity ICS ≥6 ka
DC lightning protection
Grade C:10~20KA
Configuration includes lightning protection plate
150AWall mounted power supply system Dimensions: 700H * 350D * 580W, including temperature control system  

 

Environmental condition

  

Environmental parameters
Environmental conditions for use Transportation environmental conditions Storage environmental conditions conform to notes
type parameter unit Relevant standards
Weather external temperature low temperature -40 -40 -25 YD/T1058-2000中 "-40℃ Can start at full load,
high temperature 45 70 55 4.1.1and4.1.2 "+55~+65℃Linear derating20%.
temperature variation ℃/min / 1 / ETS300019-2-2T2.3  
humidity relative humidity % 5-90 90(40±2℃) / YD/T1058-2000中4.1.3 Short term testing requirements: 0-95%, maximum value of 95%, non condensing
  air pressure low pressure Kpa 86 70 70 YD/T1058-2000中4.1.4 Only apply to modules
  high atmospheric pressure Kpa 106 106 106  
altitude m ≤4000 When the altitude exceeds 2000m, for every 100m increase, the temperature decreases by 0.5 ℃

 

 

Electrical characteristics

  

 
 
1 Input characteristics
 
Serial Number project technical requirement unit notes
1.1 Input Voltage 90—300 Vac 176-300Vac full load output, 90-175Vac reduced load output
1.2 Input maximum current 57 A  
1.3 Input Rated Voltage 220 Vac Phase voltage
1.4 Input voltage frequency 47—63(The typical value is50/60) Hz  
1.5 Input power factor ≥0.99   Full load working state
 
 
2 output characteristic
 
Serial Number project technical requirement Unit notes
2.1 Output rated voltage -54 Vdc IN220Vac
2.2 Output voltage range -42— -58 Vdc Adjustable through monitoring (test condition: no load)
2.3 Output rated current 150 A  
2.4 Output Rating Power 8.7 KW  
2.5 Output ripple and noise ≤200 mVp-p The oscilloscope bandwidth should be20MHz,
Probe parallel with 10u+104 capacitor
2.6 Startup output delay 3—8 S IN 220Vac,
2.7 Voltage stabilization accuracy ≤±1%    
2.8 Noise index Broadband clutter ≤100 mV 3.4—150 KHz
Sound voltage ≤30 mV 150—30 MHz
Telephone balance weight ≤2 mV  
noise voltage
2.9 dynamics overshoot amplitude △V:≤5 %Vo 25%—50%—25%
in response to recovery time △t:≤500 µS 50%—75%—50%load change
2.1 Unequal current distribution ≤5%   Module parallel 50% -100% rated output
(Functional modules can work in parallel)
2.11 temperature coefficient ±0.02 %/℃  
2.12 output efficiency ≥95%   220Vac/Rated load (typical value), high-efficiency module
≥92%   220Vac/Rated load (typical value), universal module
≥87%   110VAC/rated load
 
 
3 Alarm and Protection Points
 
Serial Number project technical requirement Unit notes
3.1 System input overvoltage cut-off 298±5 VAC Automatically recoverable, recovery point290V±5V
3.2 Module input overvoltage protection ≥300 VAC  
3.3 System input undervoltage cut-off 80±5 VAC 可自动恢复,恢复点136V±5V
3.4 Module input undervoltage protection ≤85 VAC  
3.5 Input overvoltage alarm 275 VAC Restore the difference to 10V, default value
3.6 Input undervoltage alarm 175 VAC Restore the difference to 10V, default value
3.7 Output overvoltage alarm -58.0V Vdc Recovery difference of 0.5V, default value
3.8 Output undervoltage alarm -47.0V Vdc Recovery difference of 0.5V, default value
3.9 Output overvoltage protection 2 Vdc Cannot be automatically restored
3.1 One time power-off protection -46 Vdc  
3.11 Secondary power-off protection -43.2 Vdc  
3.12 Battery powered on automatic   greater than50Vdc
           
Safety regulations and EMC characteristics    
           
Serial Number
project Standard (or testing conditions) notes
1 Anti electric Input-- Output 3000Vac/30mA/1min, No arcing, no breakdown (system requirement)
strength (Can withstand 50Hz) During testing, the lightning protection unit, monitoring module, and rectifier module should be removed, and the relative humidity should be ≤ 90% when the ambient temperature is 15-35 ℃
  Input - Earth 1500Vac/30mA/1min,  
  (Can withstand 50Hz)  
  Input - Earth 500Vac/30mA/1min,  
2 isolation Input-- Output ≥10MΩ@500Vdc During testing, remove the lightning protection unit, monitoring module, and rectifier module, and conduct the test at an ambient temperature of 15-35 ℃ and a relative humidity of ≤ 90%
resistance Input - Earth ≥10MΩ@500Vdc
Input - Earth ≥10MΩ@500Vdc
3 Audio noise ≤55dB  
4 Leakage current If the leakage current of a single module<3.5mA system exceeds this value, it will be labeled as' large leakage current must be grounded first '  
5 Radiation disturbance emission CLASS A EN55022
Conducted harassment emission CLASS A EN55022
Current harmonic emission CLASS A(Rectifier module) IEC61000-3-2
6 Electrostatic discharge immunity air discharge 8KV, IEC61000-4-2
Contact discharge6KV,
Radiated electromagnetic field immunity LEVEL 3 IEC61000-4-3
Electrical fast pulse group immunity LEVEL 4 IEC61000-4-4
Surge immunity LEVEL 4 判 IEC61000-4-5
Conductive immunity LEVEL 3 IEC61000-4-6
Voltage sag, short-term Select according to standards IEC61000-4-29
Interruption and buffering immunity
Voltage fluctuation and flicker PST:<1.00,PST<0.65,DC<3%, IEC61000-3-3
DMX:<4%, d(t):<0.2S(module)

 

Company Details

Bronze Gleitlager

,

Bronze Sleeve Bushings

 and 

Graphite Plugged Bushings

 from Quality China Factory
  • Business Type:

    Manufacturer,Seller

  • Year Established:

    2019

  • Total Annual:

    700000-1000000

  • Employee Number:

    50~100

  • Ecer Certification:

    Verified Supplier

Shenzhen Daxin Intelligent Equipment Technology Co., Ltd. – Powering the Future with Innovation Company Overview DaXin Smart Equipment is a leading manufacturer of critical power infrastructure solutions , specializing in: UPS & Backup Power Systems (1kVA–800kVA) 5G/Telecom P... Shenzhen Daxin Intelligent Equipment Technology Co., Ltd. – Powering the Future with Innovation Company Overview DaXin Smart Equipment is a leading manufacturer of critical power infrastructure solutions , specializing in: UPS & Backup Power Systems (1kVA–800kVA) 5G/Telecom P...

+ Read More

Get in touch with us

  • Reach Us
  • Shenzhen Daxin Intelligent Equipment Technology Co., Ltd
  • Green Base Industrial Park, Longtian Street, Pingshan District, Shenzhen
  • https://www.power-cabinets.com/

Leave a Message, we will call you back quickly!

Email

Check your email

Phone Number

Check your phone number

Requirement Details

Your message must be between 20-3,000 characters!

Submit Requirement