Payment Terms | 912$/piece |
Supply Ability | 1piece in stock |
Delivery Time | 3 day |
Packaging Details | 160*110*60mm |
System | gold-plated contacts |
No dead space | yes |
Weight[g] | 520.1 |
Dimensions[mm] | 153 x 100 x 57 |
Brand Name | IFM |
Model Number | PG2794 |
Certification | 3C |
Place of Origin | GERMANY |
View Detail Information
Explore similar products
IFM Inductive Full-metal Sensor II502A IIK3010-BPKG/AM/US104DPS/3G/3D Connector
Inductive Sensor IIS206 IIKC015BASKG/2LED Flush Mountable Connector 1 X M12
IIS238 Inductive Sensor IfmElectronic For Industrial Mobile Cooling And
IFM Electronic Gmbh Inductive Sensor IM0010 Non-flush Mountable
Product Specification
Payment Terms | 912$/piece | Supply Ability | 1piece in stock |
Delivery Time | 3 day | Packaging Details | 160*110*60mm |
System | gold-plated contacts | No dead space | yes |
Weight[g] | 520.1 | Dimensions[mm] | 153 x 100 x 57 |
Brand Name | IFM | Model Number | PG2794 |
Certification | 3C | Place of Origin | GERMANY |
High Light | Flush pressure sensor ,Analog Display pressure sensor ,PG2794 pressure sensor |
Application | ||||||||||||
Application | hygienic systems | |||||||||||
Media | viscous media and liquids with suspended particles; liquids and gases | |||||||||||
Medium temperature [°C] | -25...125; (145 max. 1h) | |||||||||||
Pressure rating | 50 bar | 725 psi | ||||||||||
Min. bursting pressure | 150 bar | 2175 psi | ||||||||||
Type of pressure | relative pressure | |||||||||||
No dead space | yes | |||||||||||
Electrical data | ||||||||||||
Operating voltage [V] | 18...32 DC | |||||||||||
Current consumption | [mA] | < 70; (24 V) | ||||||||||
Min. insulation resistance [MΩ] | 100; (500 V DC) | |||||||||||
Protection class | III | |||||||||||
Reverse polarity protection | yes | |||||||||||
Power-on delay time [s] | 6 | |||||||||||
Integrated watchdog | yes | |||||||||||
ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen — We reserve the right to make technical alterations without prior notice. — EN-GB — PG2794-00 — 11.07.2016 | ||||||||||||
PG2794 | ||||||||||||
Flush pressure sensor with analogue display | ||||||||||||
PG-010-REA01-MFRKG/US/ /P | ||||||||||||
Inputs / outputs | ||||||||||||
Number of inputs and outputs | Number of digital outputs: 1; Number of analogue outputs: 1 | |||||||||||
Outputs | ||||||||||||
Total number of outputs | 2 | |||||||||||
Output signal | switching signal; analogue signal; (configurable) | |||||||||||
Electrical design | PNP/NPN | |||||||||||
Number of digital outputs | 1 | |||||||||||
Output function | normally open / normally closed; (parameterisable) | |||||||||||
Max. voltage drop switching output DC |
[V] | 2 | ||||||||||
Permanent current rating of switching output DC |
[mA] | 250 | ||||||||||
Switching frequency DC | [Hz] | 50 | ||||||||||
Number of analogue outputs | 1 | |||||||||||
Analogue current output | [mA] | 4...20, invertible; (scalable) | ||||||||||
Max. load | [Ω] | (Ub - 10 V) / 20 mA | ||||||||||
Short-circuit protection | yes | |||||||||||
Type of short-circuit protection |
pulsed | |||||||||||
Overload protection | yes | |||||||||||
Measuring/setting range | ||||||||||||
Measuring range | -1...10 bar | -14.5...145 psi | ||||||||||
Set point SP | -0.98...16 bar | -14.2...232 psi | ||||||||||
Reset point rP | -1...15.98 bar | -14.5...231.8 psi | ||||||||||
Analogue start point | -1...13.5 bar | -14.5...195.7 psi | ||||||||||
Analogue endpoint [bar] | 1.5...16 | |||||||||||
Insteps of | 0.01 bar | 0.1 psi | ||||||||||
Accuracy / deviations | ||||||||||||
Switch point accuracy [% of the span] |
< ± 0,2; (Turn down 1:1) | |||||||||||
Repeatability | [% of the span] | < ± 0,1; (with temperature fluctuations < 10 K; Turn down 1:1) | ||||||||||
Characteristics deviation [% of the span] |
< ± 0,2; (Turn down 1:1 linearity, incl. hysteresis and repeatability limit value setting to DIN 16086) |
|||||||||||
Linearity deviation | [% of the span] | < ± 0,15; (Turn down 1:1) | ||||||||||
Hysteresis deviation [% of the span] |
< ± 0,15; (Turn down 1:1) | |||||||||||
Long-term stability | < ± 0,1; (Turn down 1:1; per year) | |||||||||||
[% of the span] | ||||||||||||
Temperature coefficient zero point [% of the span / 10 K] |
< ± 0,05; (0...70 °C) | |||||||||||
Temperature coefficient span [% of the span / 10 K] |
< ± 0,15; (0...70 °C) | |||||||||||
ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen — We reserve the right to make technical alterations without prior notice. — EN-GB — PG2794-00 — 11.07.2016 | ||||||||||||
PG2794 | ||||||||||||
Flush pressure sensor with analogue display | ||||||||||||
PG-010-REA01-MFRKG/US/ /P | ||||||||||||
Response times | ||||||||||||
Response time | [ms] | < 10 | ||||||||||
Damping for the switching output dAP |
[s] | 0.01...30 | ||||||||||
Damping for the analogue output dAA |
[s] | 0.01...30 | ||||||||||
Step response time analogue output |
[ms] | 25 | ||||||||||
Operating conditions | ||||||||||||
Ambient temperature [°C] | -25...80 | |||||||||||
Storage temperature Protection |
[°C] | -40...100 IP 67; IP 69K |
||||||||||
Tests / approvals | ||||||||||||
EN 61000-4-2 ESD | 4 kV CD / 8 kV AD | |||||||||||
EN 61000-4-3 HF radiated | 10 V/m | |||||||||||
EMC | EN 61000-4-4 Burst | 2 kV | ||||||||||
EN 61000-4-5 Surge | 0,5/1 kV | |||||||||||
EN 61000-4-6 HF conducted | 10 V | |||||||||||
Shock resistance | DIN IEC 68-2-27 | 50 g (11 ms) | ||||||||||
Vibration resistance | DIN IEC 68-2-6 | 20 g (10...2000 Hz) | ||||||||||
MTTF [years] | 100 | |||||||||||
Mechanical data | ||||||||||||
Weight | [g] | 553 | ||||||||||
Materials | stainless steel (1.4404 / 316L); PA; FKM; PTFE; viewing glass: laminated safety glass 4 mm | |||||||||||
Materials (wetted parts) | ceramics (99.9 % Al2O3); PTFE; stainless steel (1.4435 / 316L); surface characteristics: Ra < 0,4 / Rz 4 |
|||||||||||
Min. pressure cycles | 100 million | |||||||||||
Process connection | threaded connection G 1 external thread Aseptoflex Vario | |||||||||||
Displays / operating elements | ||||||||||||
Display | Display unit | 2 x LED, green | ||||||||||
switching status | LED, yellow | |||||||||||
switch points | LED ring | |||||||||||
function display | alphanumeric display, 4-digit | |||||||||||
measured values | analogue display, 0...350° rotatable, pointer not visible when unit disconnected |
|||||||||||
measured values | alphanumeric display, 4-digit | |||||||||||
With scale | yes | |||||||||||
Extended display range (max.) |
16 bar | 232 psi | ||||||||||
Remarks | ||||||||||||
Remarks | characteristics deviation in the extended display range: 1.5 % of the span | |||||||||||
switch point accuracy in the extended display range: 1.5 % of the span | ||||||||||||
Pack quantity | 1 pcs. | |||||||||||
Electrical connection | ||||||||||||
Connector: 1 x M12; Contacts: gold-plated |
Company Details
Business Type:
Trading Company
Year Established:
2017
Total Annual:
300000-800000
Employee Number:
12~20
Ecer Certification:
Verified Supplier
Xiamen Zhicheng Automation Technology Co., Ltd Xiamen Zhicheng Automation Technology Co., Ltd. Still Working And Able To Shipping Worldwide.We Are The Supplier For Industrial Automation Spare Parts.we Specialize In Plc Module, Dcs Card Pieces, Esd System C... Xiamen Zhicheng Automation Technology Co., Ltd Xiamen Zhicheng Automation Technology Co., Ltd. Still Working And Able To Shipping Worldwide.We Are The Supplier For Industrial Automation Spare Parts.we Specialize In Plc Module, Dcs Card Pieces, Esd System C...
Get in touch with us
Leave a Message, we will call you back quickly!