Payment Terms | L/C, D/A, D/P, T/T, Western Union, MoneyGram |
Delivery Time | 3-5work days |
Target gases | Refrigerant gas R-32 |
Circuit voltage | 5.0±0.2V DC |
Output voltage | 3.50V typical in 5000ppm R-32 Malfunction condition: VOUT < 0.05V or VOUT > 4.95V (Vc = 5.00V) |
Reference voltage | 3.50±0.10V at 20˚C Malfunction condition: VREF < 2.50V or VREF > 3.70V (Vc = 5.00V) |
Initial alarm accuracy | 2800~7000ppm R-32 (under standard test conditions) Alarm state: VOUT ≥ VREF Normal state: VOUT < VREF |
Warm-up time | ≤60 seconds (time before VOUT < VREF after power is turned on in a clean atmosphere) |
Model Number | FCM2630-C01 |
View Detail Information
Explore similar products
H2S-AH Hydrogen Sulfide Sensor (High Current H2S Sensor) Is Used In Hydrogen
NH3-B1 Four Electrode Electrochemical Ammonia Sensor (NH3 sensor) Is Used In
H2S-B4 High Resolution Hydrogen Sulfide Sensor (H2S sensor) Is Used To Monitor
NO2-A1 Nitrogen Dioxide Sensor (Portable NO2 Sensor) For Nitrogen Dioxide
Product Specification
Payment Terms | L/C, D/A, D/P, T/T, Western Union, MoneyGram | Delivery Time | 3-5work days |
Target gases | Refrigerant gas R-32 | Circuit voltage | 5.0±0.2V DC |
Output voltage | 3.50V typical in 5000ppm R-32 Malfunction condition: VOUT < 0.05V or VOUT > 4.95V (Vc = 5.00V) | Reference voltage | 3.50±0.10V at 20˚C Malfunction condition: VREF < 2.50V or VREF > 3.70V (Vc = 5.00V) |
Initial alarm accuracy | 2800~7000ppm R-32 (under standard test conditions) Alarm state: VOUT ≥ VREF Normal state: VOUT < VREF | Warm-up time | ≤60 seconds (time before VOUT < VREF after power is turned on in a clean atmosphere) |
Model Number | FCM2630-C01 | ||
High Light | Refrigeration Systems Gas Sensor Module ,Analog Output Gas Sensor Module |
FCM2630-C01 Gas Sensor Module Pre-calibrated Module Is Used For Refrigerant Leak Detection In Refrigeration Systems Refrigerant Gases R-32 Factory Calibrated Analog Output
Features:
* Factory calibrated
* Temperature compensation circuit
* Resistant to interference gases
* Analog output
* Meets IEC60335-2-40 and JRA4068 requirements
Applications:
* Refrigerant gas leak detection in air
conditioning/refrigeration systems
FCM2630-C01* is an embedded type module using the semiconductor gas
sensor TGS2630 which is optimized to detect A2L refrigerant gas R-32.
This module enables users to easily build a reliable gas leakage detection
system by eliminating electronic circuit design for temperature compensation
and the calibration process. In addition, a connector allows easy replacement
of the gas sensor module for periodic maintenance.
The TGS2630 gas sensor has a built-in filter to reduce the influence of alcohol
and other interference gases, resulting in high selectivity to R-32. For more
detailed information on the gas sensor, including sensitivity characteristics,
see TGS2630 Product Information.
FCM2630-C01 is capable of satisfying the IEC60335-2-40 Edition 6.0 Annex LL and the JRA4068:2021
(Performance 3) standards. The applicable standards are both limited to refrigerant gas type R-32.
* FCM Series is the model name of refrigerant gas sensor modules supplied by Figaro Engineering Inc.
Power consumption | approx. 0.3W |
Weight | approx. 4g |
Dimensions | 25 x 25 x 16mm |
Test gas conditions | 20˚±2˚C, 65±5%RH |
Circuit conditions | Vc = 5.00±0.05V DC |
Company Details
Business Type:
Manufacturer,Trading Company
Year Established:
2006
Total Annual:
900000-1000000
Employee Number:
50~80
Ecer Certification:
Verified Supplier
Yijiajie Electronics is a full range of silicon pressure sensors from the United States, FREESCALE/, GE, MEAS, SMI, and a full range of sensing and control products from the United States HONEYWELL pressure, temperature and humidity, gas flow, current, Hall effect, etc., Japan HAMAMATSU flame, UV se... Yijiajie Electronics is a full range of silicon pressure sensors from the United States, FREESCALE/, GE, MEAS, SMI, and a full range of sensing and control products from the United States HONEYWELL pressure, temperature and humidity, gas flow, current, Hall effect, etc., Japan HAMAMATSU flame, UV se...
Get in touch with us