Supply Ability | 50 units/Month |
Delivery Time | 12 |
type | 11kv Ring Main Unit |
name | SF6 switchgear |
model | HXGN15 |
standard | CB,ISO |
Voltage | 12 24 36KV |
Current | 630,1250A |
Brand Name | KNKONG |
Model Number | HXGN15 |
Certification | CB,ISO |
Place of Origin | China |
View Detail Information
Explore similar products
24kv GIS Ring Main Unit SF6 Gas Insulated Switchgear
HXGN15 12KV 24KV 36KV Medium Voltage Gas Insulated Switchgear
KNKONG 12KV RMU SF6 Gas Insulated Switchgear GB ISO IEC
11KV SF6 Gas Insulated Switch 2000A Ring Main Unit Panel
Product Specification
Supply Ability | 50 units/Month | Delivery Time | 12 |
type | 11kv Ring Main Unit | name | SF6 switchgear |
model | HXGN15 | standard | CB,ISO |
Voltage | 12 24 36KV | Current | 630,1250A |
Brand Name | KNKONG | Model Number | HXGN15 |
Certification | CB,ISO | Place of Origin | China |
High Light | 1250A 11kv Ring Main Unit ,SF6 MV Gis Switchgear ,11kv indoor switchgear |
Product Introduction
General
HXGN15 series unit type SF6 ring net cabinet with SF6 load switch as main switch, for whole cabinet is suitable for electric distribution automation and compact also expandable metal close switchgear. It characters in its simple structure, flexible operation, reliable interlocking and convenient installation etc., which can provide the satisfactory technical projects both for different application occasions and users. With the adoption of sensor technology and the protection relay up to date, plus the advanced technology and flexible assembly project, HXGN15 unit type SF6 ring net cabinet can completely meet the requirement of continuously variable market. It can take self-produced FLBS36 SF6 load break switch ; also according to user’s demand can be assembled with the internationally top-ranking VB4 series vacuum circuit breaker with permanent magnetic mechanism made by AREVA or HD4 type SF6 circuit breaker made by AREVA or HD4 type SF6 circuit breaker made by ABB or with our VS1-12 type vacuum circuit breaker with permanent magnetic mechanism. Operational methods for the main switch inside ring main unit can be either manual or electric power driven. And It can meet the requirement of Four Controls” when matched with FTU and RTU.
Feature
1. Metal-clad and fully enclosed structure, can prevent dirt and small animals from entrance.
2. Through the observation windows in the door panel, switch position and general condition can be clearly viewed.
3. The door and switch operating handle are mechanically interlocked to ensure the door cannot be opened with the switch closed and the switch cannot be closed with the door open.
4. The switchgear use vacuum switches combined with solid insulation material. This environmentally-friendly technology avoid the uses of SF6 as an insulation gas.
5. Reliable FIVE-PREVENTION interlock can effectively prevent from mal-operation.
Service Environment
1. Air temperature: -35℃~+40℃
2. Humidity: Monthly average humidity 95%; Daily average humidity 90% .
3. Altitude2500m
4. Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.
5. No frequent violent shake
Technical Date
No. | Item | Unit | Parameter | |||
1 | Rated voltage | kV | 12 | 24 | 36 | |
2 | Rated frequency | Hz | 50/60 | |||
3 | Rated current | A | 630(1250*) | |||
4 |
1min Power frequency withstand voltage |
wet | kV | 38 | 50 | 70 |
dry | kV | 48 | 60 | 85 | ||
5 | Lightning impulse withstand voltage | kV | 75 | 125/150 | 170 | |
6 | Rated short circuit breaking current (peak) | kA | 80 | 63 | 63 | |
7 | Rated active load and close circuit breaking current | A | 63 | 50 | 50 | |
8 | Rated transferring current | A | 1700 | 1200 | 1200 | |
9 | Rated short circuit making current (peak) | kA | 80 | 63 | 63 | |
10 | Rated cable(line) charging breaking current | A |
50 and 10 50/10 |
|||
11 | Cable charge breaking current in earthing fault | A | 20 | 20 | 20 | |
12 | Rated withstand current (peak) | kA | 80 | 63 | 63 | |
13 | Short time withstand current (2s) | kA | 25 | 20 | 20 | |
14 | Mechanism life | times | 5000 | 2000 | 2000 |
Note: For short circuit breaking and peak current is based on Fuse plus combination
Company Details
Business Type:
Manufacturer
Year Established:
2012
Total Annual:
1000000-9000000
Employee Number:
50~100
Ecer Certification:
Active Member
Knkong Electric Co., Ltd (Zhengzhou Knkong Mechanical And Electrical Co., Ltd)was established in 2012. A wholly-owned subsidiary of Henan Sanhe Electric Group. We are mainly responsible for overseas market exporting, electronic components, and technology import. Relying on a h... Knkong Electric Co., Ltd (Zhengzhou Knkong Mechanical And Electrical Co., Ltd)was established in 2012. A wholly-owned subsidiary of Henan Sanhe Electric Group. We are mainly responsible for overseas market exporting, electronic components, and technology import. Relying on a h...
Get in touch with us
Leave a Message, we will call you back quickly!