Packaging Details | Wooden Case |
Delivery Time | 35 days |
Payment Terms | TT/LC |
Supply Ability | 300 |
Place of Origin | China |
Brand Name | Shengdi Electrical |
Certification | ISO9001:2008 |
Model Number | HS3103 |
View Detail Information
Explore similar products
2-Position Meter Test Bench,0.1 accuracy class,testing single and three phase
HS-3303 Three Phase Energy Meter Test Equipment with 3 Position Meter Rack
Portable Three-phase electrical meter test set,5mA~120A,100VA output capacity,1
HS-3303 Three Phase Portable Energy Meter Test Equipment,3 Position,Max.120A
Product Specification
Packaging Details | Wooden Case | Delivery Time | 35 days |
Payment Terms | TT/LC | Supply Ability | 300 |
Place of Origin | China | Brand Name | Shengdi Electrical |
Certification | ISO9001:2008 | Model Number | HS3103 |
HS3103 Portable 1 Phase Energy Meter Test Equipment
Technical specification
1. Electrical output
1) Voltage and current measurement range
Output voltage ranges: 57.7V/63.5V and 220V/240V (480V option)
Output current ranges: 0.1A, 1A, 5A, 20A, and 100A
2) Output load capacity
Voltage loop: Max. 50VA
Current loop: Max 100VA (Measurement range 100A)
2. Electrical output adjustment
1) Voltage adjustment
a) Adjustment range: 0%~125% selected voltage range
b) Adjustment fineness: four finenesses as 10%, 1%, 0.1%, and 0.01% are
available
c) Max. output voltage: 300V or 600V
2) Current adjustment
a) Adjustment range: 0%~120% selected current range
b) Adjustment fineness: four finenesses as 10%, 1%, 0.1%, and 0.01% are
available
c) Max. output current: 120A
3) Phase adjustment
a) Adjustment fineness: 0°~359.99°
b) Adjustment fineness: four finenesses as 10°, 1°, 0.1°, and 0.01° are
Available
3. Voltage and current output distortion
This device’s voltage and current output distortion will not be more than 1%
(testing under linear load)
4. Output power stability
This device’s pre-set output power will not exceed 0.05% compared with the
measurement range variation within 180S.
5. Harmonic content
a) Number of harmonic waves: 2~31
b) Harmonic content: less than 40% (compared with fundamental wave)
c) Harmonic phase: 0°~359.99°
6. Monitoring instrument
To be read directly from the standard meter.
7. Electric pulse
Electric pulse output from standard meter:
1) For error calculator to calculate the error of any meter to be tested;
2) For the reference of upper-level measurement examination and
determination agency when sending the standard meter to them for testing.
Please refer to standard meter’s Table of Constants for pulse constants.
8. Power supply
Single-phase AC 220V/240V (100V/110V/230V is also applicable), 50/60Hz,
max. input power consumption: 500W.
Contact: Yeli
Email: hysdsales@gmail.com
Skype: lily19850618
Company Details
Business Type:
Manufacturer,Exporter
Year Established:
2007
Total Annual:
5,000,000-10,000,100
Employee Number:
200~500
Ecer Certification:
Active Member
We are the manufacturer of HS Series Single & Three-Phase Energy meter Test Bench. HS-6103 Single-Phase energy meter test device(bench) Multi-function,Double Loop. HS-6303 Three-Phase energy meter test bench ... We are the manufacturer of HS Series Single & Three-Phase Energy meter Test Bench. HS-6103 Single-Phase energy meter test device(bench) Multi-function,Double Loop. HS-6303 Three-Phase energy meter test bench ...
Get in touch with us
Leave a Message, we will call you back quickly!