China factories

China factory - Zhejiang Shengdi Technology Inc.

Zhejiang Shengdi Technology Inc.

  • China
  • Active Member

Leave a Message

we will call you back quickly!

Submit Requirement
China HS-3163P Portable single-phase energy meter Test Equipment,Max.60A internal
China HS-3163P Portable single-phase energy meter Test Equipment,Max.60A internal

  1. China HS-3163P Portable single-phase energy meter Test Equipment,Max.60A internal
  2. China HS-3163P Portable single-phase energy meter Test Equipment,Max.60A internal
  3. China HS-3163P Portable single-phase energy meter Test Equipment,Max.60A internal
  4. China HS-3163P Portable single-phase energy meter Test Equipment,Max.60A internal

HS-3163P Portable single-phase energy meter Test Equipment,Max.60A internal

  1. MOQ: 1 Piece
  2. Price: USD$1~100000/SET
  3. Get Latest Price
Supply Ability 50 pieces/month
Delivery Time 15 -20 work days.
Packaging Details WOODEN CASE
Safty IP50
Accuracy 0.1% Class
Current MAX.60A
Weight 7 KG.
Brand Name SHENGDI TECHNOLOGY
Model Number HS-3163P
Certification ISO9001
Place of Origin CHINA

View Detail Information

Contact Now Ask for best deal
Get Latest Price Request a quote
  1. Product Details
  2. Company Details

Product Specification

Supply Ability 50 pieces/month Delivery Time 15 -20 work days.
Packaging Details WOODEN CASE Safty IP50
Accuracy 0.1% Class Current MAX.60A
Weight 7 KG. Brand Name SHENGDI TECHNOLOGY
Model Number HS-3163P Certification ISO9001
Place of Origin CHINA

HS-3163P Portable single-phase test system is a high-performance calibrating instrument which is designed with international new digital technology. This test system consists of an integrated single-phase wide range voltage & current source and a single-phase electronic reference standard meter of accuracy class 0.05%. It is wide measuring range, 0.05% class high accuracy ,high tolerance to unwanted external influences and more utility functions.

HS-3163P is mainly used on-site to test energy meter’s installation,running and analyze power system.

Main technical features

  • Internal small single-phase current source which synchronized with on-site voltage;
  • Outputs 0-16A current, meets user’s multiple model, multi-load point check.
  • Can connect with current clamps, uses to on-site online calibration;
  • Adopted ARM 32-bits core embedded system, and with 7 inch TFT LCD TOUCHED SCREEN;
  • HMI design, full screen touched operation, can continue to calibrate automatically according to the scheme;
  • Can save test data for 1000 energy meters;
  • Can be used as a reference standard meter or single-phase calibration device;
  • Small size, low weight, low consumption, high accuracy and portable;
  • Support Bluetooth, and can be controlled by APP (on phone or PC);
  • With self-protection, sound and light alarm functions when current overload.

Main measurement functions

  • Independent generation of single-phase current loading conditions for verification of meters using the incoming supply voltage or internal independent generation of single phase voltage.
  • Active,reactive and apparent energy measurement with integrated error calculator and pulse output;Or with 3D and adjustable scanning head (Optional).
  • Automatically test creeping error,starting-up error,basic error and standard deviation error etc.;
  • Support energy constants verification or dial testing;
  • Support daily timing error testing;
  • Support current harmonic influence value testing;
  • When calibration, user can choose testing points freely, also can make calibration scheme freely;
  • Testing data can be saved in instrument and inquiry, and allow data import& export;
  • Can display vector diagram, harmonic spectrum and wave form to analyze power system;
  • Measure voltage, current directly or by current clamps;
  • Measureactive,reactive power and apparent power;
  • Measure phase angle,PF and frequency;

Application Range

  • Calibrate different types of energy meters before they are installed on-site;
  • Analyze energy meter running condition and error data;
  • Used for R&D and maintenance test;
  • Test and monitor power system.

2,General Technical Index

Auxiliary power supply 198 VAC … 253 VAC / 47 … 63 Hz
Power consumption 200 VA
Shell Hard plastic
Dimension 355 x 272 x 166 mm(W*H*D)
Weight ≤7KGS( not including spare parts)
Working Temp. -10 °C +50 °C
Storage Temp. -20 °C … +60 °C
R.H. ≤85%,≤21°C

3,Voltage source technical standard

Output voltage range/power 20 V … 300 V / 20 VA
Resolution 0.001 V
THD ≤ 0.5%
Stability ≤ 0.05% (3 min.)
Adjust range 0% … 120%(240V)
Frequency range accuracy resolution
45 Hz – 65 Hz ±0.01 Hz 0.01 Hz

4,Current source technical standard

Output current range/power 5 mA … 60 A / 50 VA

 

Current output(Terminal)

current range Smax / Umax
0.1 A 5 mA … 100 mA 0.6 VA / 6 V
1 A 0.1 A … 1 A 5 VA / 5 V
10 A 1 A … 10 A 12 VA / 1.2 V
50 A 10 A … 50 A 50 VA / 1 V
Resolution 0.01%*range
THD ≤ 1%
Stability ≤ 0.05% (3 min.)
Adjust range 0% … 120%
Phase angle range accuracy resolution
0°…359.99° 0.2° 0.1°
Frequency

 

 

range accuracy resolution
45 Hz – 65 Hz ±0.01 Hz 0.01 Hz
           

5,Reference standard meter technical standard

5.1,Measurement range

Measurement range input/ sensor
Voltage 10 V … 300 V U
Current 5 mA … 60 A I
10 mA … 120 A clamp 20A,100A

5.2,Voltage and current measurement accuracy

voltage / current ≤±E[%]1 2
Measurement range class
Voltage 100 V … 300 V

 

10 V … 100 V

0.05

 

0.2

Current 20 mA … 60 A

 

5 mA … 20 mA

0.05

 

0.2

Clamp 10% ≤ RG ≤ 120%

 

1% ≤ RG < 10%

0.2

 

0.5


5.3,Energy measurement accuracy

Power/energy voltage:100 V … 300 V ≤±E[%]1 2 3
Measurement /output current range class
Active power(P),apparent power(S)
Output 20 mA … 60 A

 

5 mA … 20 mA

0.05

 

0.2

Clamp 10% ≤ RG ≤ 120%

 

1% ≤ RG < 10%

0.2

 

1.0

Reactive power(Q)
Output 20 mA … 60 A

 

5 mA … 20 mA

0.1

 

0.2

Clamp 10% ≤ RG ≤ 120%

 

1% ≤ RG < 10%

0.4

 

1.0

Magnetic influence:≤0.07 % / 0.5 mT³(45 Hz … 66 Hz);

Temp. coefficient(TC):
range ≤ ±TC[%/℃] 3
0 … +40 0.02
-10 … +50 0.05

 

5.4,Frequency,phase,PF measurement accuracy

F/Phase angle/PF ≤ ±E
Measurement range  
F 45 HZ … 65 Hz 0.01 Hz
θ 0.00° … 359.99° 0.1°
PF -1.000 … +1.000 0.002

remarks:

  1. x.x: Related to measurement value

x.x: Related to measurement range(Max range,FS),E(M)=FS/M*x.x( for example: 0.2, FS =46 v, E(10V) = 46/10 * 0.2 = 0.92 %)

  1. Basic frequency range: 45 … 65 Hz
  2. S:x.x,P,Q:x.x/ PF

 

5.5,Pulse input/output

Input TTL 3 … 6 VDC
Input F Max.200 kHz
Output TTL 5 VDC
Pulse width ≥ 10μs
Constants:

 

Active power,reactive,apparent power

[imp/kWh(kvarh,kVAh)]

C = 1×109/In’;In’= In×(100%,50%,25%)

 

Constants depends on internal ranges(In)

Details see constants table

  Current In[A]
Measurement 0.1 1 10 50
100%In 50%In 25%In
Output F C’= C/3600000[imp/Ws(vars,Vas)]

 

fo = C’×P∑(Q∑,S∑)

fmax = 16.666kHz

             

6,Others

Position 1
COM. port RS232,Bluetooth
Energy error indication range -99.999%~+2000.0%
Other functions Victor diagram display,error display,harmonic analysis display

 

 

Company Details

Bronze Gleitlager

,

Bronze Sleeve Bushings

 and 

Graphite Plugged Bushings

 from Quality China Factory
  • Business Type:

    Manufacturer,Exporter

  • Year Established:

    2007

  • Total Annual:

    5,000,000-10,000,100

  • Employee Number:

    200~500

  • Ecer Certification:

    Active Member

We are the manufacturer of HS Series Single & Three-Phase Energy meter Test Bench. HS-6103 Single-Phase energy meter test device(bench)                Multi-function,Double Loop. HS-6303 Three-Phase energy meter test bench       ... We are the manufacturer of HS Series Single & Three-Phase Energy meter Test Bench. HS-6103 Single-Phase energy meter test device(bench)                Multi-function,Double Loop. HS-6303 Three-Phase energy meter test bench       ...

+ Read More

Get in touch with us

  • Reach Us
  • Zhejiang Shengdi Technology Inc.
  • #8,Zhenghua Road,Wuyuan Industry Zone,Haiyan County
  • http://metertesting-biz.ecer.com/

Leave a Message, we will call you back quickly!

Email

Check your email

Phone Number

Check your phone number

Requirement Details

Your message must be between 20-3,000 characters!

Submit Requirement