Payment Terms | L/C, T/T |
Delivery Time | 30 days |
Packaging Details | Plywood |
Workpiece | High Voltage Switch Gears |
Vacuum chamber | 1pc |
Reject point | 5.0E-6mbar.L/sec. |
Helium Recovery Rate | ≥98% |
Brand Name | HongCe |
Model Number | HC |
Certification | Calibration Certificate(cost additional) |
Place of Origin | China |
View Detail Information
Explore similar products
Automatic 15KW Helium Leak Testing Equipment For EV Power Battery Chamber Type
Manully Helium Sniffer Test for Products Assembly Line With Helium Charging And
Fully Automatic Vacuum Chamber Helium Leak Testing Equipment for Automotive Air
Two Chamber Vacuum Helium Leak Testing Equipment for Automotive Air Conditioning
Product Specification
Payment Terms | L/C, T/T | Delivery Time | 30 days |
Packaging Details | Plywood | Workpiece | High Voltage Switch Gears |
Vacuum chamber | 1pc | Reject point | 5.0E-6mbar.L/sec. |
Helium Recovery Rate | ≥98% | Brand Name | HongCe |
Model Number | HC | Certification | Calibration Certificate(cost additional) |
Place of Origin | China | ||
High Light | helium leak test equipment ,helium leak testing |
Auto Helium Leak Detection Equipment For High Voltage Switch Gears With SF6 Filling System
Product Introduction:
According to the basic leak detection principle of helium, the system uses helium as the tracer gas, helium filled into the helium chamber, and then detect the leak within the helium signal through the helium leak detector, can quickly and accurately determine the leakage accuracy of the workpiece
Technical Parameters:
Workpiece | High Voltage Switch Gears |
Vacuum chamber | 1pc, 2300*1000*1850mm |
Detectability | Each chamber can test 1-3 workpieces at the same time) |
Tracer gas | 100% Helium |
Test Cycle | 1 hour /chamber |
SF6 filling pressure | 0.04MPa (GP) |
Helium Detection Pressure | 0.04MPa (AP) |
Reject point | 5.0E-6mbar.L/sec. |
Helium Filling Time | ≥70s |
Helium Recovery Rate | ≥98% |
Picture for Reference:
Application
The system is suitable for air tightness detection and helium filling of SF6 High Voltage Switch Gears. It mainly refers to filling helium into workpieces, processing helium recovery filling SF6 gas into workpiece within the specified time, then control the filling pressure to guarantee the qualified rate of the product.
Operation process
The system has 1 vacuum chamber. The operator puts the workpiece into the fixture in the vacuum chamber, connects the workpiece interface with the quick connector, and turn on the button to close the chamber. After the door closes, the system can automatically complete the whole process like vacuum, gross leakage, helium filling, Fine leak detection, helium recovery, SF6 filling and so on.
Company Details
Business Type:
Manufacturer
Year Established:
2003
Employee Number:
50~100
Ecer Certification:
Verified Supplier
Guangzhou HongCe Equipment Co., Ltd (hereinafter referred to as HongCe) is located in Guangzhou, China, since 2003, engaged in developing and providing test equipment and detection system for electronic & electrical products, house appliances and other products. HongCe is professionally dedicate... Guangzhou HongCe Equipment Co., Ltd (hereinafter referred to as HongCe) is located in Guangzhou, China, since 2003, engaged in developing and providing test equipment and detection system for electronic & electrical products, house appliances and other products. HongCe is professionally dedicate...
Get in touch with us
Leave a Message, we will call you back quickly!