3/3 phase UPS | Online LF UPS with isolation transformer |
Packaging Details | wooden packing as export standards |
Delivery Time | 3-4 weeks after payment |
Payment Terms | TT/LC at sight |
Supply Ability | 500 units / month |
Warranty | 2years after shipment,10years technical support |
Product Name | low frequency ups |
Phase | 3phase +N+G |
Voltage | 380VAC/400V±25% or 208v+/-25% |
Frequency | 50/60Hz±4hz(Line Mode),50/60Hz±0.1Hz(battery mode) |
Floating voltage | 410/432VDC |
Input /output device | Terminal Block |
Place of Origin | China |
Brand Name | HRD/OEM |
Certification | CE,ISO,TUV |
Model Number | PV10-200KVA |
View Detail Information
Explore similar products
10KV - 400KVA Online Low Frequency UPS / HRD PV Network UPS
3 Phase Online Low Frequency Ups / 10KVA - 120KVA 50HZ Energy UPS
Medical Online Low Frequency UPS , Double Conversion 100KVA To 800KVA
3 Phase Online Low Frequency UPS 100-800kVA
Product Specification
3/3 phase UPS | Online LF UPS with isolation transformer | Packaging Details | wooden packing as export standards |
Delivery Time | 3-4 weeks after payment | Payment Terms | TT/LC at sight |
Supply Ability | 500 units / month | Warranty | 2years after shipment,10years technical support |
Product Name | low frequency ups | Phase | 3phase +N+G |
Voltage | 380VAC/400V±25% or 208v+/-25% | Frequency | 50/60Hz±4hz(Line Mode),50/60Hz±0.1Hz(battery mode) |
Floating voltage | 410/432VDC | Input /output device | Terminal Block |
Place of Origin | China | Brand Name | HRD/OEM |
Certification | CE,ISO,TUV | Model Number | PV10-200KVA |
High Light | online lowe frequency ups ,online ups power ,3 phase low frequency ups |
Large Power Online Low Frequency UPS , 3 Phase UPS 10KVA - 200KVA
Introduction:
POWERVALUE SERIES 3/3phase large power UPS(10kVA-200kVA), offer advanced DSP control, high speed 16 bits digital IC, DDC control technology, also use advanced high power IGBT and SCR, it is a digital, Informationization, Networking, Online Intelligent Pure Sine-wave Uninterruptible Power Supply, which is based on reliable, advanced, high efficiency digital/analog hybrid technology. POWERVALUE
3:3 phase SERIES can supply stable complete protection for your critical equipment.
Ideal Application:
Finance, Telecom, Insurance, Traffic, Taxation, Military, Security, Energy, Education, Government, Industry, etc.
Features&Benefits:
Pure sine wave output,true online double conversion
Output with isolation transformer
7 inch color LCD
Can be set to ECO mode
With EPO function
Can be with 100% unbalance load
Adopt the fourth layer PCB,and SMD technology
Sixth generation IGBT, much higher efficiency, lower temperature, more reliable
Full protection, overload, over voltage, short circuit, over temperature etc
Cold start
Generator compatible
EVENT LOG 256 LOGS
Advanced parallel function
With RS232 and RS485 standard collocate,
Option SMMP and dry contact connection
Option battery manage function
Model |
PV3310 |
PV3320 |
PV3330 |
PV3340 |
PV3360 |
PV3380 |
PV33100 |
PV33120 |
PV33160 |
PV33200 |
||
Capacity |
10Kva |
20Kva |
30Kva |
40Kva |
60Kva |
80Kva |
100Kva |
120Kva |
160Kva |
200Kva |
||
AC INPUT |
||||||||||||
Phase |
3phase +N+G |
|||||||||||
Voltage |
380VAC/400V±25% or 208v+/-25% |
|||||||||||
Frequency |
50/60Hz±4hz(Line Mode),50/60Hz±0.1Hz(battery mode) |
|||||||||||
BYPASS INPUT |
||||||||||||
phase |
3phase +N+G |
|||||||||||
Voltage |
380VAC/400VAC or 208v (+/-15%) |
|||||||||||
Frequency |
50Hz±5%,60Hz±5% |
|||||||||||
OUTPUT |
||||||||||||
Phase |
3phase+N+G |
|||||||||||
Voltage |
380VAC/400V or 208v±1% |
|||||||||||
Frequency |
50/60Hz±10%,60Hz±10% |
|||||||||||
charging current |
3A~30A settable(depend on battery capacity) |
|||||||||||
Battery |
||||||||||||
Max.discharge current(A) |
28 |
56 |
85 |
113 |
169 |
225 |
282 |
338 |
450 |
560 |
||
Battery quantity |
30/32pcs |
|||||||||||
battery voltage |
360/384VDC(348-384V acceptable) |
|||||||||||
Floating voltage |
410/432VDC |
|||||||||||
Charging current |
3A~30A(0.1C according to battery capacity)settable |
|||||||||||
Nominal voltage |
380V/400VAC±1%(steady load),380V/400VAC±5%(load fluctuate) |
|||||||||||
Nominal frequency |
50Hz±0.05%,60Hz±0.05%(battery supply power) |
|||||||||||
Frequency |
<±0.05% (un Synchronization);<±2% (Synchronization) |
|||||||||||
Crest factor |
3:1 |
|||||||||||
Total harmonic distortion |
Linearity load <3%;non-linearity load<5% |
|||||||||||
Dynamic load voltage transient |
<±5%(from 0 to 100% abrupt change) |
|||||||||||
Moment restart time |
<10ms |
|||||||||||
Balance load voltage |
<±1%;<±5%(imbalance load voltage) |
|||||||||||
Overload capability |
125% 1min,150% 1S |
|||||||||||
Efficiency |
>82%(at 100% load) |
|||||||||||
Working temperature |
0~40℃ |
|||||||||||
Humidity |
0%~90%(non~condensing) |
|||||||||||
Type of cooling |
Forced draught |
|||||||||||
Noise dB |
40~50(1m) |
45~55(1 m) |
55~60(1m) |
60~65(1m) |
||||||||
Physical |
||||||||||||
Case color |
Gray /black(option) |
|||||||||||
Input cable |
The bottom / back |
|||||||||||
Dimension W×D×H(mm) |
600*620*1200 |
600*720*1460 |
950*820*1780 |
1380*850*1780 |
||||||||
G .W(kg) |
225 |
250 |
310 |
350 |
410 |
550 |
850 |
920 |
1320 |
1670 |
||
Input /output device |
Terminal Block |
|||||||||||
All specification subject to change without further notice
Company Details
Business Type:
Manufacturer,Exporter
Year Established:
2010
Total Annual:
15,000,000-200,00,000
Employee Number:
300~500
Ecer Certification:
Verified Supplier
About HRD ,founded in 2010, after more than 14 years fast development,HRD has grown into a large leading professional UPS manufacturer with ISO9001:2015 , ISO14001,ISO18001 certified Based on strong high level professional R&D team with... About HRD ,founded in 2010, after more than 14 years fast development,HRD has grown into a large leading professional UPS manufacturer with ISO9001:2015 , ISO14001,ISO18001 certified Based on strong high level professional R&D team with...
Get in touch with us
Leave a Message, we will call you back quickly!