Payment Terms | T/T, L/C, MoneyGram, Western Union |
Delivery Time | 5-20 working days |
Packaging Details | Wooden Case |
Supply Ability | 500sets/month |
V distortion | <1.0% |
Work time | 60 minutes once at rated conditions |
Q factor | Q≥30(f=45Hz) |
Output wave | Since wave |
F range | 30Hz~300Hz |
System accuracy | 1.5% |
Brand Name | GDZX |
Model Number | ZXBXZ-54/54 |
Certification | ISO9001 |
Place of Origin | CHINA |
View Detail Information
Explore similar products
Reactive Power Full Compensated 380v Resonant Test System For Generator
110kV Power System High Voltage Hipot Tester , Hipot Test Set High Mechanical
AC High Voltage Resonance Test Series 1.5% System Accuracy Three Phase 380V 50Hz
135kVA 108KV AC High Voltage Resonant Test System With Since Output Wave
Product Specification
Payment Terms | T/T, L/C, MoneyGram, Western Union | Delivery Time | 5-20 working days |
Packaging Details | Wooden Case | Supply Ability | 500sets/month |
V distortion | <1.0% | Work time | 60 minutes once at rated conditions |
Q factor | Q≥30(f=45Hz) | Output wave | Since wave |
F range | 30Hz~300Hz | System accuracy | 1.5% |
Brand Name | GDZX | Model Number | ZXBXZ-54/54 |
Certification | ISO9001 | Place of Origin | CHINA |
High Light | ac resonant test system ,hipot test equipment |
This series devices are designed for AC withstand voltage test of substation primary equipment under 550KV or below, mainly composed of variable-frequency power supply, exciting transformer, reactor and capacitive Voltage divider
Features:
1. rated voltage:
27kV--- meets AC withstand voltage test of 10kV cable
working frequency 30-300Hz
Test voltage is not more than 22kV, test time is 5min;
54kV--- meets AC withstand voltage test of 35kV cable
Working frequency 30-300Hz
Test voltage is not more than 52kV, the test time is 60min;
2. output voltage waveform distortion rate: <1.0%
3. allow continuous working hours: one time working for 60 minutes under rated conditions;
4. Quality factor of the device: Q > 30 (f=45Hz)
5. device output waveform: sine wave
6. input power supply: three phase 380V or single phase 220V
7. frequency regulation range: 30Hz ~ 300Hz
8. system measurement precision: 1.5%
9. over voltage, over current, zero start and other protection functions.
COMPOSITION
1. Frequency conversion power supply
(1) rated power: 3kW
(2) Input voltage: three phase 380V or single phase 220V + 5% 50Hz
(3) output voltage: 0 ~ 400V
(4) Output voltage frequency: 30 ~ 300Hz
(5) 0.1Hz regulation step
(6) Frequency instability is less than 0.02%
(7) Output current: 0 ~ 7.5A
2. High voltage reactor (2 units)
(1) rated working voltage: 27kV |
3. excitation transformer
(1) rated capacity: 3kVA |
4. capacitance divider (1 units)
(1) self capacitance: 1500pF |
5. test line (1 sets)
Configuration Test object | Reactor 2 sections 27kVA/27kV | Excitation transformer output terminal | Test voltage(kV) |
35kV/300mm²/0.4km
| Series connection | 3kV | ≤52kV |
10kV/300mm²Cable 1km
| Parallel connection | 1.5kV | ≤22kV |
Company Details
Business Type:
Manufacturer,Exporter
Year Established:
2012
Total Annual:
8 million-10 million
Employee Number:
100~120
Ecer Certification:
Verified Supplier
About GDZX Wuhan GDZX Power Equipment Co.,Ltd. is located in Wuhan, China, covering an area of 50 acres, with 6,000 m2 of factory space and 12,000 m2 of office buildings. We specialize in power testing equipment, engineering services, equipment commissioning, ope... About GDZX Wuhan GDZX Power Equipment Co.,Ltd. is located in Wuhan, China, covering an area of 50 acres, with 6,000 m2 of factory space and 12,000 m2 of office buildings. We specialize in power testing equipment, engineering services, equipment commissioning, ope...
Get in touch with us
Leave a Message, we will call you back quickly!