Payment Terms | T/T |
Supply Ability | 10units/2months |
Delivery Time | 25~45 Work Days |
Packaging Details | Export Standard Wooden Case With Fumigation Free |
Test principle | Variable frequency resonant circuit |
Test Item | AC withstand voltage test under 45KV , 270KV |
Max.capacity | 270KVA |
Max. voltage | 45KV , 270KV |
Design feature | Portable Type , Lighter Single Piece Weight, Special for On-site Installation and test |
Component: | V/F Power Source, Excitation Transformer,lighter Modular Test Reactor, And Voltage Divider |
Test frequency | 30-300Hz |
Duty cycle | 60 mints |
Test accuracy | No less than 1.5% |
Output waveform | Good sine wave |
Test object | 35KV/10KV short cable , 110KV power substation |
Test standard | IEC 60060-1:2010;IEC 62271-203:2011 for GIS, IEC 60840:2011 for XLPE cable; |
Brand Name | Fanke High-voltage |
Model Number | CHX-270KVA/45KV,270KV |
Certification | ISO9001 |
Place of Origin | China |
View Detail Information
Explore similar products
High Accuracy Hv Voltage Tester , High Voltage Apparatus For Power Substation
810KVA High Voltage Test Kit , 35KV And 132KV Hv Cable Testing Equipment 30
132KV GIS Testing AC Resonant Test System Lighter Single Piece Weight
FKVF Series High Voltage Testing Of Electrical Equipments 5KW~400KW Capacity
Product Specification
Payment Terms | T/T | Supply Ability | 10units/2months |
Delivery Time | 25~45 Work Days | Packaging Details | Export Standard Wooden Case With Fumigation Free |
Test principle | Variable frequency resonant circuit | Test Item | AC withstand voltage test under 45KV , 270KV |
Max.capacity | 270KVA | Max. voltage | 45KV , 270KV |
Design feature | Portable Type , Lighter Single Piece Weight, Special for On-site Installation and test | Component: | V/F Power Source, Excitation Transformer,lighter Modular Test Reactor, And Voltage Divider |
Test frequency | 30-300Hz | Duty cycle | 60 mints |
Test accuracy | No less than 1.5% | Output waveform | Good sine wave |
Test object | 35KV/10KV short cable , 110KV power substation | Test standard | IEC 60060-1:2010;IEC 62271-203:2011 for GIS, IEC 60840:2011 for XLPE cable; |
Brand Name | Fanke High-voltage | Model Number | CHX-270KVA/45KV,270KV |
Certification | ISO9001 | Place of Origin | China |
High Light | high voltage resonant test system ,resonant test set |
Portable Variable Frequency Resonant Withstand Voltage Test Set , For 35KV Cable and 110KV Power Substation Test
I. Product Usage :
This test set model CHX-270KVA/45KV, 270KV is designed for 10KV / 35KV class short XLPE cable ,power transformer, CB,CT/PT, busbar in 110KV power substation to perform on-site AC withstand voltage test with variable frequency resonant circuit technology; the highest test voltage is no more than 45KV ,90KV,270KV; test frequency: 30-300Hz; the duty cycle is no more than 60mints. it can help customers to perform preventive test or hand-over test on AC withstand voltage test
Test range of the set is as following:transformer
1. 1000m of 35kV/300mm2 cable, test frequency 30-300Hz, test voltage 52kV, test time 5min.
2, 3000m of 10kV/300mm2 cable , test frequency 30-300Hz, test voltage 22kV, test time 5min.
3, 35kV/31500kVA main transformer , capacitance ≤ 0.015uF, test frequency 40-300Hz, test voltage 68kV, test time 1min.
4, 110kV/50000kVA main transformer , capacitance ≤ 0.015uF, test frequency 40-300Hz, test voltage 160kV, test time 1min.
4, CB,CT/PT, busbar in 110KV power substation , test frequency 40-300Hz, test voltage no more than 265, test time 1min.
The whole test set consists of variable frequency power source , excitation transformer , 6pieces of reactors, and high voltage measurement devider(capacitive voltage divider). This type of test set is most suitable for 35KV or 110KV power sub-station
II. General Technical Data
III. Main Components:
SN | Name of Components | Type and specification | Qty. | Each weight | Each Dimension |
1 | Variable frequency power | FKVF-20kW/380V | 1piece | 35kgs | 480*480*520mm |
2 | Excitation transformer | CQSB(J)-15kVA/2.5KV,10KV | 1piece | 130kgs | 500*500*580mm |
3 | HV resonant test reactor | CHX(kf)-45kVA/45kV | 6pieces | 55kgs | D420*H480mm |
4 | Capacitive divider | TRF-270kV/1000pF | 1set | 30kgs | D200*H2150mm |
5 | Special test accessories | 1set |
IV. Test priciple :
VF: Variable Frequency Power Source T : Excitation Transformer
L : Test Reactor Cx: Tested Equipment MOA1: Lightning Arrestor
C1,C2: Voltage divider(C1 is high voltage arm,C2 is low voltage arm )
V. Main Measuring and control software panel:
Note: This is the software panel before start test for parameter setting
VI.Accessories
VII. Other Optional Model
1. For GIS on-site test
Model | Rated voltage | Rated output current | Rated output capacity | Application (From 45Hz starting) |
CHX-135KVA/135KV | 27KV*5 | 1A | 135KVA | For 72.5KV and below GIS |
CHX-270KVA/135KV | 27KV*5 | 1A | 135KVA | For 72.5KV and below GIS |
CHX-216KVA/216KV | 27KV*8 | 1A | 216KVA | For 123KV and below GIS |
CHX-270KVA/270KV | 27KV*10 | 1A | 270KVA | For 145KV and below GIS |
CHX-275KVA/275KV | 275KV | 2A | 275KVA | For 170KV and below GIS |
Special requirement can be made by order |
2. For 45KV XLPE cable on-site test
Model | Rated voltage | Rated output current | Rated output capacity | Max Application |
CHX-108/54 | 54KV | 2A | 108KVA | 45kV cable≤1km |
CHX-216/54 | 54KV | 4A | 216KVA | 45kV cable≤2km |
CHX-324/54 | 54KV | 6A | 324KVA | 45kV cable≤3km |
CHX-432/54 | 54KV | 8A | 432KVA | 45kV cable≤4km |
CHX-540/54 | 54KV | 10A | 540KVA | 45kV cable≤5km |
CHX-1080/54 | 54KV | 20A | 1080KVA | 45kV cable≤10km |
Special requirement can be made by order |
3. For 66KV XLPE cable on-site test
Model | Rated voltage | Rated output current | Rated output capacity | Max Application |
CHX-160/80 | 80KV | 2A | 160KVA | 66kV cable≤0.5km |
CHX-320/80 | 80KV | 4A | 320KVA | 66kV cable≤1km |
CHX-640/80 | 80KV | 8A | 640KVA | 66kV cable≤2km |
CHX-960/80 | 80KV | 12A | 960KVA | 66kV cable≤3km |
CHX-1280/80 | 80KV | 16A | 1280KVA | 66kV cable≤4km |
CHX-1600/80 | 80KV | 20A | 1600KVA | 66kV cable≤5km |
CHX-3200/80 | 80KV | 40A | 3200KVA | 66kV cable≤10km |
CHX-9600/80 | 80KV | 120A | 9600KVA | 66kV cable≤20km |
Special requirement can be made by order |
VIII. On-site insulation test standard table from IEC 60840:2011 for XLPE cable
Company Details
Business Type:
Manufacturer,Exporter,Seller
Year Established:
2003
Total Annual:
6000000-10000000
Employee Number:
100~120
Ecer Certification:
Active Member
Founded in 2003, FANKE is the domestic leader specializing in designing and manufacturing HV test, measurement and overhaul equipments. In 2003, Wuhan HIGHVOLT Co.,Ltd is established as our subsidiary. We provide a diversity of complete testing solutions and one-stop service for electric power compa... Founded in 2003, FANKE is the domestic leader specializing in designing and manufacturing HV test, measurement and overhaul equipments. In 2003, Wuhan HIGHVOLT Co.,Ltd is established as our subsidiary. We provide a diversity of complete testing solutions and one-stop service for electric power compa...
Get in touch with us
Leave a Message, we will call you back quickly!