Payment Terms | L/C, D/P, Western Union, T/T, Credit card |
Supply Ability | 20000 sets per week |
Delivery Time | 10 days, subject to quantity negotiation |
Packaging Details | Plywood outer box with bubble bag or paper |
Application | B,Fire Fighting Emergency Rescue,Fire Suppression System,fire rescue system,C type fire |
Discharge time | ≤10s |
Working temperature | 0-50 degree |
Company type | manufacturer over 10-years |
Agent willingness | Negotiable |
Shipping way | By sea |
After sale service | Yes |
Filling pressure | 2.5MPa |
Brand Name | Rongxiao |
Model Number | GQQ180/2.5, GQQ150/2.5, GQQ120/2.5 ,GQQ100/2.5 ,GQQ90/2.5 ,GQQ70/2.5 ,GQQ40/2.5 |
Certification | CAL,CMA,CNAS,,CCC |
Place of Origin | Guangzhou City, Guangdong Province, China |
View Detail Information
Explore similar products
90L Type Hfc 227ea FM200 Fire Extinguishing System With Multiple Zones
Heptafluoropropane Fm200 Fire Extinguishing System 120L Red Cabinet Type
Industrial Heptafluoropropane Fire Suppression Systems Fm200 Cabinet Type
Heptafluoropropane Fm200 Fire Fighting System Single Zone Control With 90L
Product Specification
Payment Terms | L/C, D/P, Western Union, T/T, Credit card | Supply Ability | 20000 sets per week |
Delivery Time | 10 days, subject to quantity negotiation | Packaging Details | Plywood outer box with bubble bag or paper |
Application | B,Fire Fighting Emergency Rescue,Fire Suppression System,fire rescue system,C type fire | Discharge time | ≤10s |
Working temperature | 0-50 degree | Company type | manufacturer over 10-years |
Agent willingness | Negotiable | Shipping way | By sea |
After sale service | Yes | Filling pressure | 2.5MPa |
Brand Name | Rongxiao | Model Number | GQQ180/2.5, GQQ150/2.5, GQQ120/2.5 ,GQQ100/2.5 ,GQQ90/2.5 ,GQQ70/2.5 ,GQQ40/2.5 |
Certification | CAL,CMA,CNAS,,CCC | Place of Origin | Guangzhou City, Guangdong Province, China |
High Light | FM200 Gas Fire Extinguishing System ,40L Gas Fire Extinguishing System |
40L 33kg FM200 Gas Fire Extinguishing System With Multi-Zone Protection.
Maintenance and maintenance points of cabinet-type heptafluoropropane FM200
Many people don’t know how we should maintain and maintain the cabinet-type heptafluoropropane fire extinguishing device after purchasing it? So today Guangzhou Rongan Fire Protection will bring you an article about "Key Points of Maintenance and Maintenance of Cabinet-type Heptafluoropropane Fire Extinguishing Device".
In order to ensure the reliability of the cabinet-type heptafluoropropane fire extinguishing device, the user should establish a complete device inspection and maintenance system in accordance with regulations, formulate operating specifications, and have a dedicated person responsible for regular maintenance, inspection and record keeping of the device.
During the maintenance and care of the cabinet-type HFC-227ea, the relevant provisions of the "Gas Fire Extinguishing System Construction and Acceptance Specifications" must be strictly followed. The maintenance and care of the cabinet-type HFC-227ea is as follows:
1. The maintenance personnel must be trained by the company and be familiar with the structural principle, working performance, main technical parameters, operation procedures and structural principles of each component of the device.
2. Monthly maintenance and care
(1) The HFC-227ea fire extinguishing agent reserve of the device should be checked every month.
① When the pressure gauge indication value of the fire extinguishing agent storage bottle is within the green value range, it can be considered that the fire extinguishing agent reserve is normal; if the pressure gauge indication value of the fire extinguishing agent storage bottle is found to be lower than the green indication value range, the construction party should be contacted in time.
② As the ambient temperature changes, the pressure of the fire extinguishing agent storage bottle will change accordingly, which is a normal phenomenon. As long as the pressure gauge indication value on the fire extinguishing agent storage bottle is within the green indication range, it means that the storage bottle pressure is normal.
③Fire extinguishing agent filling should be done by professionals.
(2) Each component of the fire extinguishing device should be inspected monthly. If any fault or abnormality is found, it should be repaired in time.
3. The electromagnet of the device should be tested for action every year: remove the electromagnet from the container valve, energize it with the control circuit of the controller itself, and the electromagnet can continue to be used only if it works normally. If a fault occurs, it should be repaired or replaced in time.
4. The fire extinguishing agent storage bottle of the device should be tested for strength and sealing performance every three years. It can only be used after passing the test. At the same time, the container valve of the device should be tested for strength and sealing performance. It can only be used after passing the test.
5. The working status of the fire extinguishing system should be checked frequently, especially after the fire extinguishing device is sprayed, it should be reset.
(1) Reset the alarm fire extinguishing controller
(2) Reset the pressure signal device
(3) Replace the diaphragm, conduct a sealing test, and refill the fire extinguishing agent and driving gas
Company Details
Business Type:
Manufacturer
Year Established:
2013
Total Annual:
6000000-8000000
Employee Number:
120~150
Ecer Certification:
Verified Supplier
The factory is a professional manufacturer of fire-fighting facilities integrating R&D, production, design and sales services. We are committed to the research and development of HFC-227ea (FM200), Novec1230 and inert gas products. The factory is a professional manufacturer of fire-fighting facilities integrating R&D, production, design and sales services. We are committed to the research and development of HFC-227ea (FM200), Novec1230 and inert gas products.
Get in touch with us
Leave a Message, we will call you back quickly!