China Electrical Railway Protection 65KA 100KA Lightning Arrester
China Electrical Railway Protection 65KA 100KA Lightning Arrester

  1. China Electrical Railway Protection 65KA 100KA Lightning Arrester

Electrical Railway Protection 65KA 100KA Lightning Arrester

  1. MOQ: 51 PCS
  2. Price:
  3. Get Latest Price
Payment Terms T/T, Western Union
Supply Ability 500000PCS/MONTH
Delivery Time 7 Days
Packaging Details CARTONS
Rated voltage MOA 42kv
DC 1mA reference voltage ≥65kv
4/10 μs high current 65KA
Lightning impulse withstand voltage 200kv
System nominal vol 27.5kv
Power frequency dry withstand voltage 105kV
Brand Name QIUPU
Model Number HY5WT
Certification IEC
Place of Origin WENZHOU

View Detail Information

Contact Now Ask for best deal
Get Latest Price Request a quote
  1. Product Details
  2. Company Details

Product Specification

Payment Terms T/T, Western Union Supply Ability 500000PCS/MONTH
Delivery Time 7 Days Packaging Details CARTONS
Rated voltage MOA 42kv DC 1mA reference voltage ≥65kv
4/10 μs high current 65KA Lightning impulse withstand voltage 200kv
System nominal vol 27.5kv Power frequency dry withstand voltage 105kV
Brand Name QIUPU Model Number HY5WT
Certification IEC Place of Origin WENZHOU
High Light 100KA Lightning Arrester65KA Lightning ArresterRailway Protection Lightning Arrester

65KA 100KA Lightning arrester for electrified railway protection

 

 

parameter
It is used to protect various electrical equipment, contact nets, and electric locomotives of electrified railways from atmospheric overvoltage and operating voltage damage.

 

Lightning arrester model System rated voltage< lightning arrester
Rated voltage
Continuous transport
Line voltage
DC reference
Voltage(U1mA)
Residual voltage under steep wave impulse current Residual voltage under lightning impulse current Residual voltage under operating surge current Square wave flow capacity(2ms) High Current
Impact resistance
 
kV(r.m.s) ≮kV ≯kV A kA
HY5WT-42/120
27.5 42 34.0 67 138 120 98 400 65  
HY5WT-41/115 27.5 41 32.8 67 133 115 94 400 65
HY5WT-84/240 55.0 84 68.0 134 276 240 196 400 65  
HY5WT-82/230 55.0 82 65.6 134 266 230 188 400 65
HY10WT-42/120 27.5 42 34.0 66 138 120 98 400 100  
HY10WT-41/115 27.5 41 32.8 66 133 115 94 400 100
HY5WT-84/240 55.0 84 68.0 132 276 240 196 400 100  
HY5WT-82/230 55.0 82 65.6 132 266 230 188 400 100
Electrical parameter table of DC arrester
TYPE Continuous operating voltage/kV Residual voltage at nominal current/kVp
1/8μs 8/20μs 30/60μs
10kA 20kA 1kA 3kA 5kA 10kA 20kA 500A 1kA 2kA
ATSL-1 1 2.67 3.00 2.1 2.20 2.30 2.39 2.52 2.00 2.05 2.12
ATSL-2 2 5.36 5.95 4.1 4.42 4.60 4.80 5.26 3.98 4.08 4.24
ATSL-3 3 8.07 8.88 6.2 6.65 6.90 7.18 7.81 5.95 5.10 6.35
ATSL-4.2 4.2 10.9 11.9 8.6 9.18 9.50 9.95 10.9 8.32 8.78 5.95

 

Measurement of insulation resistance of lightning arrester


The measurement of insulation resistance, for the FS-type lightning arrester, is mainly to check the seal situation, if the seal is not strict will inevitably cause internal dampness, so that the insulation resistance obviously decreased. In accordance with the pre-test procedure, the measurement shall be carried out by testing the 2500V megabyte meter, and the insulation resistance shall be not less than 2500M. Clean the surface of the lightning arrester before testing, otherwise the leakage current on the coat surface will affect the accuracy of the test. For this purpose, the surface of the porcelain cover should be cleaned with a clean, absorbent cloth before the test, and a thin metal wire is used to circle the underside of the first underskirt of the coat, which is then connected to the mew watch "shield" terminal column to eliminate the effect. In the test, the Meow watch should be connected with the lightning arrester as short as possible and the electrical contact should be good. The mew watch should be placed horizontally, the speed should be uniform, and 120 revolutions per minute should be used to obtain good measurement results.

 

For FZ lightning arrester, in addition to checking whether the interior is damp, check whether the shunt resistor is broken and aging, if the shunt resistor is old and broken, because of poor contact, the insulation resistor will increase. To ensure that measurements are accurate, measurements should be made twice and the data should be compared for any changes. Measurement should be done using the same meioEurope meter at the same voltage level, otherwise comparison is not possible.

 

DC 1 mA reference voltage test


Apply 0.75 times 1 mA DC voltage(DC voltage pulsation rate not greater than 1.5 %) to both ends of the arrester when the current through the arrester is stabilized at 1 mA. The voltage at both ends of the lightning arrester shall not be less than 25 kV.

DC Leakage Current Test
After 0.75 times 1 mA DC voltage is applied at both ends of the lightning arrester at test time, the leakage current passing through the lightning arrester should not be greater than 50mA. During the test, when the leakage current reaches 30 Mu A and the voltage continues to increase, the leakage current will increase sharply. In order to prevent the effect of leakage current on the surface of the ceramic cover, the outside surface of the cover should be cleaned with a cloth with good absorbency before testing to eliminate the effect.

Measurement of conductance current of lightning arrester with parallel resistance

     

Rated Voltage Work Voltage AC Current
35KV 54kV 5A
21kV 62kV 10A

 

       

Company Details

Bronze Gleitlager

,

Bronze Sleeve Bushings

 and 

Graphite Plugged Bushings

 from Quality China Factory
  • Business Type:

    Exporter,Trading Company,Seller

  • Year Established:

    2016

  • Total Annual:

    200000-500000

  • Employee Number:

    100~120

  • Ecer Certification:

    Verified Supplier

        Wenzhou Qiupu Electric Power Co., Ltd. is located in Yueqing Economic Development Zone, Zhejiang Province. It is a high-tech enterprise specializing in the research and development, production and sales of electric power products such as circuit breakers, transformer...         Wenzhou Qiupu Electric Power Co., Ltd. is located in Yueqing Economic Development Zone, Zhejiang Province. It is a high-tech enterprise specializing in the research and development, production and sales of electric power products such as circuit breakers, transformer...

+ Read More

Get in touch with us

  • Reach Us
  • WENZHOU QIUPU ELECTRIC POWER CO., LTD.
  • ROOM 302 , BUILDING 65 , ZHENGDA CITY , NO. 555 YANHAI WEST ROAD , CHENGNAN STREET , YUEQING CITY , ZHEJIANG, PROVINCE . CHINA-325600
  • https://www.epoxyresininsulator.com/

Leave a Message, we will call you back quickly!

Email

Check your email

Phone Number

Check your phone number

Requirement Details

Your message must be between 20-3,000 characters!

Submit Requirement