Payment Terms | T/T |
Supply Ability | 10 sets/day |
Delivery Time | 1-2weeks |
Packaging Details | Reinforced Carton box with wooden tray |
Key word | Commercial Air Source Heat Pump system |
Project time | 2016 |
Sysem ender | radiator heating |
Service area | 30000M2 |
Heat pump capacity | 25HP per set |
Heat pump Quantity | 23 sets |
Brand Name | Yushen |
Model Number | SDNA-075Y |
Certification | CCC, ISO, CQC |
Place of Origin | China |
View Detail Information
Explore similar products
Copeland Scroll Compressor Heat Pump Cooling System 2100 × 1100 × 2080 Mm
62 DBA Noise Level Heat Pump Heating And Cooling AC ASHP Units With Two Fans
High Automation Heat Pump Heating And Cooling System CQC Certification
Safety Air Source Heat Pump System Radiator Ender 2100 × 1100 × 2080 Mm
Product Specification
Payment Terms | T/T | Supply Ability | 10 sets/day |
Delivery Time | 1-2weeks | Packaging Details | Reinforced Carton box with wooden tray |
Key word | Commercial Air Source Heat Pump system | Project time | 2016 |
Sysem ender | radiator heating | Service area | 30000M2 |
Heat pump capacity | 25HP per set | Heat pump Quantity | 23 sets |
Brand Name | Yushen | Model Number | SDNA-075Y |
Certification | CCC, ISO, CQC | Place of Origin | China |
High Light | air source heat pump heating system ,heat pump ac unit |
30000 M2 Hospital Indoor Heating Sytem with Air Source Heat Pump
Project Overview
The project is located at No. 4, Shandong East Road, Boshan District, Zibo City, Shandong Province, with a construction area of about 30,000 m2. The exterior wall has no insulation, and the single-layer glass window was officially put into use in 2016. It has been stable, reliable and efficient, and is generally used according to various users. The original coal is calculated to save about 532 tons of raw coal, reduce SO2 by about 9.1 tons, reduce CO2 by about 957 tons, and reduce ash and slag emissions by about 160 tons.
Project Sumary:
Project location | E 117 N 35.5 |
Heating area | 30000M2 |
Quantity of air-source heat pump | 23 sets |
Model | SDNA-075Y(25HP) |
System design | ultra low temperature air source heat pump+radiator |
Building insulation | None |
Project in use time | 2016 |
Model
Model | SDNA-075Ycode name.pdf | |||
Compressor capacity | 25HP | |||
Function | Heat | |||
Electricity | 380V 3N-50Hz | |||
Working conditions | ℃ | -25~+45 | ||
Data | Heata | Nominal capacity | KW | 44.5 |
Input power | KW | 18.3 | ||
COP | / | 2.4 | ||
Heating IPLV(H) | 2.7 | |||
A7W35c | KW/COP | 75.0/4.2 | ||
A2W35 | KW/COP | 62.5/3.20 | ||
A-7W35 | KW/COP | 52.5/3.0 | ||
A-15W55 | KW/COP | 45.5 /1.97 | ||
A-20W45 | KW/COP | 37.4/2.04 | ||
Max. running currency | A | 56 | ||
Compressor quantity | set | 2 | ||
Refrigerant/charging quantity kg | / | R22/10*2 | ||
Air blow type | / | Top | ||
Water pipe diameter | mm | 50 | ||
Rating flow | m³/h | 12.6 | ||
Water side pressure loss | kPa | ≤45 | ||
Noise level | dB(A) | 62 | ||
Overall dimensions(L×W×H) | mm | 2100×1100×2080 | ||
Weight | kg | 730 |
a: Nominal heating conditions: ambient dry bulb temperature-12℃, wet bulb temperature-14℃, outlet water temperature 41℃, water flow 0.172 * nominal heating capacity
A7W35 working condition: inlet air temperature 7℃, outlet water temperature 35℃
Company Details
Business Type:
Manufacturer
Year Established:
2014
Total Annual:
7000000-12000000
Ecer Certification:
Active Member
Shandong Yushen Energy Technology Co., Ltd. established in 2014 with a registered capital of 50.2 million RMB (about 7 million USD), is a factory specialized in research & development, design, production, sales and service of air-source heat pumps drive by its mission” Leave a clean world ... Shandong Yushen Energy Technology Co., Ltd. established in 2014 with a registered capital of 50.2 million RMB (about 7 million USD), is a factory specialized in research & development, design, production, sales and service of air-source heat pumps drive by its mission” Leave a clean world ...
Get in touch with us