Payment Terms | T/T |
Supply Ability | 10 sets/day |
Delivery Time | 1-2weeks |
Packaging Details | Reinforced Carton box with wooden tray |
Key word | Cold Heat Pump In Cold Weather |
Compressor capacity | 3HP |
Function | Cooling and heating |
Air blow type | Side |
Suitable working conditions | -25C~+45C |
Electricity | 220V-3N-50hz |
Brand Name | Yushen |
Model Number | SLNA-009U(P) |
Certification | CCC, ISO, CQC |
Place of Origin | China |
View Detail Information
Explore similar products
Lab Building Central Air Source Heat Pump High COP Under -13F Winter
Freon R404a Home Air Source Heat Pump One Compressor Electricity AC Outdoor Unit
Automatic Cold Climate Air Source Heat Pump , Split System Heat Pump
7kw Cold Climate Air Source Heat Pump , Mini Split Heat Pump Fan Outdoor Unit
Product Specification
Payment Terms | T/T | Supply Ability | 10 sets/day |
Delivery Time | 1-2weeks | Packaging Details | Reinforced Carton box with wooden tray |
Key word | Cold Heat Pump In Cold Weather | Compressor capacity | 3HP |
Function | Cooling and heating | Air blow type | Side |
Suitable working conditions | -25C~+45C | Electricity | 220V-3N-50hz |
Brand Name | Yushen | Model Number | SLNA-009U(P) |
Certification | CCC, ISO, CQC | Place of Origin | China |
High Light | all climate heat pump ,heat pump in cold weather |
3HP Cold Heat Pump In Cold Weather / All Climate Heat Pump -25C~+45℃
Cold Heat Pump In Cold Weather Features
(1) The air source heat pump system has no cooling water system, no cooling water consumption, and no power consumption of the cooling water system. In addition, there have been many reports of Legionella infections caused by cooling water pollution. From the perspective of safety and hygiene, considering air source heat pumps also has obvious advantages.
(2) Air source heat pump system Because the boiler is not needed, the corresponding boiler fuel supply system, dust removal system and flue gas emission system are not needed, the system is safe and reliable, and has no pollution to the environment.
Yushen Cold Climate Heat Pump Systems Advantages
1. long heating time and less defrosting time,35% more powerful than other products
2. Automatic testing line,100% finished products testing
3. More than 6 million M2 heating area project cases all over the different latitude area.
Cold Heat Pump In Cold Weather Parameter
a: Nominal heating conditions: ambient dry bulb temperature-12℃, wet bulb temperature-14℃, outlet water temperature 41℃, water flow 0.172 * nominal heating capacity
b:Nominal refrigeration conditions: ambient dry bulb temperature 35℃, outlet water temperature 7℃, water flow 0.172 * nominal cooling capacity
c:A7W35 working condition: inlet air temperature 7℃, outlet water temperature 35℃
Model | SLNA(B)-009U(P)Cold Climate Heat Pump Systems code name.pdf | |||
Compressor capacity | 3HP | |||
Function | Heating and Cooling | |||
Data | Heata | Nominal capacity | KW | 5.8 |
Input power | KW | 2.52 | ||
COP | / | 2.3 | ||
Heating IPLV(H) | 2.53 | |||
Coolb | Nominal capacity | KW | 6.5 | |
Input power | KW | 2.6 | ||
COP | / | 2.5 | ||
Cooling IPLV(C) | 2.7 | |||
A7W35c | KW/COP | 9.2/4.10 | ||
A2W35 | KW/COP | 8.0/3.6 | ||
A-7W35 | KW/COP | 5.9/2.7 | ||
A-15W55 | KW/COP | 5.0/1.90 | ||
A-20W45 | KW/COP | 4.5/1.95 | ||
Max. running currency | A | 18 | ||
Compressor quantity | set | 1 | ||
Refrigerant/charging quantity kg | / | R404A/2.2 | ||
Air blow type | / | Side | ||
Water pipe diameter | inch | G1〞 | ||
Rating flow | m³/h | 1.6 | ||
Water side pressure loss | kPa | ≤35 | ||
Noise level | dB(A) | 59 | ||
Overall dimensions(L×W×H) | mm | 1087×435×901 | ||
Weight | kg | 70 |
Company Details
Business Type:
Manufacturer
Year Established:
2014
Total Annual:
7000000-12000000
Ecer Certification:
Active Member
Shandong Yushen Energy Technology Co., Ltd. established in 2014 with a registered capital of 50.2 million RMB (about 7 million USD), is a factory specialized in research & development, design, production, sales and service of air-source heat pumps drive by its mission” Leave a clean world ... Shandong Yushen Energy Technology Co., Ltd. established in 2014 with a registered capital of 50.2 million RMB (about 7 million USD), is a factory specialized in research & development, design, production, sales and service of air-source heat pumps drive by its mission” Leave a clean world ...