Payment Terms | T/T, Alipay, Paypal |
Supply Ability | 1000pcs per week |
Delivery Time | Negotiable |
Packaging Details | carton |
Manufacturer | MTL Instruments |
Product No. | MTL5532 |
Product type | Pulse Isolator |
Number of channels | One, fully floating |
Alarm output | Relay ON in alarm, 0.5A @ 35Vdc max. |
Sensor type | Switch or proximity detector (NAMUR/BS EN 60947–5–6:2001) 2– or 3–wire voltage or pulse transmitter |
Location of switch | Zone 0, IIC, T6 hazardous area Div. 1, Group A, hazardous location |
Shipping weight | 2 Kg |
Brand Name | MTL |
Model Number | MTL5532 |
Certification | HART |
Place of Origin | UK/China |
View Detail Information
Explore similar products
MTL5561 MTL Instruments MTL Fire & Smoke Detector Interface
MTL5576-RTD MTL Instruments | 2ch Temperature converter, RTD
MTL5576-THC MTL Instruments Temperature Converter Number Of Channels Two
MTL5522 MTL Instruments Solenoid / Alarm Driver Number of channels One
Product Specification
Payment Terms | T/T, Alipay, Paypal | Supply Ability | 1000pcs per week |
Delivery Time | Negotiable | Packaging Details | carton |
Manufacturer | MTL Instruments | Product No. | MTL5532 |
Product type | Pulse Isolator | Number of channels | One, fully floating |
Alarm output | Relay ON in alarm, 0.5A @ 35Vdc max. | Sensor type | Switch or proximity detector (NAMUR/BS EN 60947–5–6:2001) 2– or 3–wire voltage or pulse transmitter |
Location of switch | Zone 0, IIC, T6 hazardous area Div. 1, Group A, hazardous location | Shipping weight | 2 Kg |
Brand Name | MTL | Model Number | MTL5532 |
Certification | HART | Place of Origin | UK/China |
High Light | MTL Instruments 20mA ,MTL Instruments 4mA ,mtl5532 pulse isolator |
MTL5532 MTL Instrument Pulse Isolator
The MTLx532 isolates pulses from a switch, proximity detector, current
pulse transmitter or voltage pulse transmitter located in a hazardous
area. It is ideal for applications involving high pulse rates and fast
response times, by repeating the pulses into the safe area. An analogue
output proportional to frequency is also provided, together with a relay
output, which may be configured to act as an alarm. Configuration is
carried out with a personal computer.
SPECIFICATION
See also common specification
• Number of channels
One, fully floating
• Sensor type
Switch or proximity detector (NAMUR/BS EN 60947–5–6:2001)
.2– or 3–wire voltage or pulse transmitter
• Location of switch
Zone 0, IIC, T6 hazardous area
Div. 1, Group A, hazardous location
• Location of proximity detector or transmitter
Zone 0, IIC, T4–T6 if suitably certified
Div.1, Group A, hazardous location
• Input
Switch input:
Output ON if switch is closed
Proximity detector input:
Excitation: 7.0 to 9.0V dc from 1kΩ nominal
Output ON if input > 2.1mA* (< 2kΩ)
Output OFF if input < 1.2mA* (> 10kΩ)
Switching hysteresis: 0.2mA (650Ω) nominal
*NAMUR and BS EN 60947–5–6:2001standards
Current pulse input:
Transmitter supply: 16.5V dc at 20mA
Short circuit current: 24mA
Output: Iin > 9.0mA = ON, Iin < 7.0mA = OFF
Switching hysteresis: 0.5mA
Voltage pulse input
Input impedance: > 10kΩ
Switching point voltage (Vsp): 3, 6, or 12V nominal
(User selectable by switches on the side of the module)
Output: Vin > Vsp = ON, Vin < Vsp = OFF
Switching hysteresis: 100mV + (0.1 x Vsp) typical
• Safe-area pulse output
Maximum delay: 10µs
Maximum off–state voltage: 35V
Maximum off–state leakage current: 10µA
Maximum on–state resistance: 25Ω
Maximum on–state current: 50mA
Output OFF if supply fails
Note: LFD signal is Zener-diode protected against inductive loads
• Safe-area current output
Input capture delay: 2 signal periods (5ms min.)
Signal range: 4 to 20mA
Under/over range: 0 to 22mA
Load resistance: 0 to 450Ω @20mA
Output resistance: >1MΩ
Ripple: < 50µA peak-to-peak
Accuracy: better than 20µA at 20°C
Temperature drift: < 1µA/°C
Risetime (10% - 90%, after step change): 60 ms
• Alarm output
Relay ON in alarm, 0.5A @ 35Vdc max.
• Pulse width
High: 10µs min
Low: 10µs min
• Frequency range
0 – 50kHz - pulse output mode
0 – 10KHz - for analogue output
• LED indicators
Green: power indication
Yellow: on when output circuit is on
Red: flashing when line fault or error
• Power requirement
65mA at 24V dc
70mA at 20V dc
55mA at 35V dc
• Power dissipation within unit
1.35W maximum at 24V
1.75W maximum at 35V
• Safety description (Um = 253V rms or dc)
Terminals 2 to 1 and 6 to 1
Uo=10.5V Io=14mA Po=37mW
Terminals 4 to 3 and 1
Uo=28V Io=93mA Po=651mW
Terminals 3 to 1
Non-energy-storing apparatus ≤1.5V, ≤0.1A and ≤25mW; can be
connected without further certification into any IS loop with an open-circuit voltage <28V
Terminals 5 to 4 and 1
Vmax ≤ 28V, Imax ≤ 94mA, Pmax ≤ 0.66W
• Configurator
A personal computer running MTL PCS45 software with a PCL45USB serial interface.
Related Models:
HCU16 | MTL5521 |
HCU3700 | MTL5522 |
HM64RIB20-1.0 | MTL5531 |
HM64RIB20-1.5 | MTL5532 |
HMM64 | MTL5541 |
HMRIB16-1.0 | MTL5541S |
HMS64 | MTL5544 |
HTP-SC32 | MTL5544D |
MTL4044D | MTL5546 |
MTL4511 | MTL5546Y |
MTL4516 | MTL5561 |
MTL4516C | MTL5573 |
MTL4521 | MTL5575 |
MTL4541 | MTL5582B |
MTL4541 | MTL7728+ |
MTL4544 | MTL7756AC |
MTL4544D | MTL7760AC |
MTL4546Y | MTL7761PAC |
MTL4549Y | MTL7765AC |
MTL4573 | MTL7787+ |
MTL4575 | MTL7787P+ |
MTL4646Y | MTLCPS16 |
MTL4850 | NJ5-18GK-N |
MTL4851 | SD150X |
MTL4852 | SD32 |
MTL5018 | SD32X |
MTL5032 | SDRTD |
MTL5042 | SLP32D |
MTL5044 | TP48-3-I-NDI |
MTL5049 | TP48-3-N-NDI |
MTL5511 | TP48-4-I-NDI |
MTL5514D | TP48-4-N-NDI |
MTL5516 | TP48-N-NDI |
MTL5516C | ZB24571 |
Company Introduction:
Achievers Automation Limited has more than 10 years experience in the market of Industrial Automation, specialized in reselling factory sealed Probe, Sensor, DCS,isolator barrier, HMI, PLC,Adapter,Profibus connector and cable from Brands as BENTLY NEVADA, Endress+Hauser, YOKOGAWA,MTL,Allen-Bradley, Pepperl+Fuchs,Rosemount, ASCO, Schneider, Lenze, Pro-face, Mitsubishi, Omron, Lenze, Delta, Honeywell, Siemens and etc. If you have any request, please do not hesitate to contact us.
FAQ of Achievers
Q:Are the Products Genuine OEM Units?
A: These items have been certified by Achievers Automation Limited to be genuine OEM Units obtained through OEM or independent third-party channels.
Q:How will you arrange shipment?
A: We can arrange shipment based on your request. We have cooperated forwader who can arrange shipment via FedEx, DHL,TNT with good price.
Q:What is the warranty of goods?
A: One-year Warranty.
Company Details
Business Type:
Distributor/Wholesaler,Trading Company
Year Established:
2012
Total Annual:
3000000-5000000
Employee Number:
10~15
Ecer Certification:
Verified Supplier
Achievers Automtation Limited deals with a complete range of industrial automation components and instruments with more than 12 years’ experience, and always try best to provide quality goods and timely services to our valued customers from over 45 countries worldwide. Achievers s... Achievers Automtation Limited deals with a complete range of industrial automation components and instruments with more than 12 years’ experience, and always try best to provide quality goods and timely services to our valued customers from over 45 countries worldwide. Achievers s...
Get in touch with us
Leave a Message, we will call you back quickly!